Gossen Metrawatt GmbH 43
SECUTEST ST BASE(10) / PRO and SECULIFE ST BASE(25)
13.19 Measurements with Test Adapter
1
Differential current method only with test instruments
including feature I01 (e.g. SECUTEST ST PRO)
2
Alternatively AT3-IIS or AT3-II S32 for IPE and IE
Please read and observe the operating
instructions for the test adapters regard-
ing correct connection of the test
adapter and the DUT, as well as pecu-
liarities involved in the test procedure.
Connection Example with EL1
Connection Example with VL2E
Connection Example for Measuring Protective Con-
ductor Current IPE
1
(direct method) with AT3-IIIE
Connection Example for Measuring Device Leak-
age Current IG
1
(differential current method) with
AT3-IIIE
1
Only with feature I01(e.g. SECUTEST ST PRO or SECULIFE ST BASE(25))
Test with Adapter
EL1 VL2E AT3-
IIIE
2
AT16DI
AT32DI
CEE
adapter
Connectors for the DUT
Non-heating devices,
1P+N+PE 16 A
— ✔✔ — —
Earthing contact,
1P+N+ PE 16 A
— ✔ — — —
CEE, 1P+N+PE 16 A
— ✔✔ — ✔
CEE, 3P+N+PE 16 A
— ✔✔✔ / — ✔
CEE, 3P+N+PE 32 A
— ✔✔— / ✔✔
5 x 4mm sockets
——— — ✔
Connectors for the test instrument
Earthing contact,
1P+N+ PE 16 A
—— ✔✔ —
Socket for test probe
— ✔✔ ——
Plug for V–COM
1
—— ✔ ——
Active test
Protective conductor current IPE
– Direct method
—— ✔✔ —
– Differential current
——✔
1
✔ —
Device leakage current IE
– Direct method
—— ✔✔ —
– Differential current
——✔
1
✔ —
Touch current T
—— ✔✔ —
Passive test
Pro. con. resistance
RPE
✔✔ ✔ ✔ ✔
Insulation resistance
RINS
✔✔ ✔ ✔ ✔
Protective conductor cur-
rent
IPE
(equivalent leak-
age current method)
— ✔✔ ✔ ✔
Extension cords:
the following measurements, in addition to RPE
& RINS, are performed in switch position
EL1
Single-phase (3-pole)
✔✔ ✔ ——
3-phase (5-pole)
— ✔✔ ——
Wire short-circuit
✔✔ ✔ ——
Wire break
✔✔ ✔ ——
Reversed wires
— ✔✔ ——