EasyManua.ls Logo

Gossen MetraWatt PROFITEST INTRO - Optional Accessories (Not Included); Periodic Testing Per DGUV Regulations 3 (Formerly BGV A3); Limit Values for Electrical Systems and Operating Equipment

Gossen MetraWatt PROFITEST INTRO
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GMC-I Messtechnik GmbH 57
19.3 Periodic Testing per DGUV Regulations 3 (formerly BGV A3)
– Limit Values for Electrical Systems and Operating Equip-
ment
Limit Values per DIN VDE 0701-0702
Maximum Allowable Limit Values for Protective Conductor
Resistance for Connector Cables with Lengths of up to 5 m
1
This value may not exceed 1 for permanently connected data processing sys-
tems (DIN VDE 0701-0702).
2
Total protective conductor resistance: max. 1
Minimum Allowable Limit Values for Insulation Resistance
* With activated heating elements (where heating power > 3.5 kW and R
INS
< 0.3
M: leakage current measurement is required)
Maximum Permissible Limit Values for Leakage Current in mA
* For devices with heating power of greater than 3.5 kW
Note 1: Devices which are not equipped with accessible parts that are
connected to the protective conductor, and which comply with re-
quirements for housing leakage current and, if applicable, patient
leakage current, e.g. computer equipment with shielded power
pack
Note 2: Permanently connected devices with protective conductor
Note 3: Portable X-ray devices with mineral insulation
Key
I
B
Housing leakage current (probe or touch current)
I
DI
Residual current
I
SL
Protective conductor current
Maximum Permissible Limit Values for Equivalent Leakage Current in
mA
1
For devices with heating power 3.5 kW
19.4 Optional Accessories (not included)
Master Battery Pack (material no. Z502H)
8 LSD NiMH rechargeable batteries with reduced self-
discharging (AA), 2000 mAh with sealed cells
Charger (material no. Z502R)
Broad-range charger for charging NiMH batteries in
the measuring instrument
Input: 100 to 240 V AC, output: 16.5 V DC, 0.6 A
ISO Calibrator 1 (material no. M662A)
Calibration adapter for testing the accuracy of instru-
ments used for measuring insulation resistance and
low-resistance for test voltages of up to 1000 V (per
VDE 0413, parts 1, 2, 4 and 10).
PRO-Schuko measuring adapter (material no. Z503K)
Single-phase, country-specific measuring adapter for
the PROFITEST INTRO, earthing contact plugs to three
4 mm safety plugs (black, blue, yellow-green), 300 V
CAT III, 16 A, touch-guarded
PRO-CH measuring adapter (material no. Z503M)
Single-phase, country-specific measuring adapter for
the PROFITEST INTRO, earthing contact plugs to three
4 mm safety plugs (black, blue, yellow-green), 300 V
CAT III, 16 A, touch-guarded
PRO-GB measuring adapter (material no. Z503N)
Single-phase, country-specific measuring adapter for
the PROFITEST INTRO, earthing contact plugs to three
4 mm safety plugs (black, blue, yellow-green), 300 V
CAT III, 16 A, touch-guarded
PRO-JUMPER (material no. Z503J)
Touch-guarded short-circuit adapter for the
PROFITEST INTRO
for measurement cable compensation
PRO-JUMPER-CH (material no. Z503P)
Touch-guarded short-circuit adapter for the
PROFITEST INTRO
for measurement cable compensation
PRO-JUMPER-GB (material no. Z503R)
Touch-guarded short-circuit adapter for the
PROFITEST INTRO
for measurement cable compensation
1081 Probe (material no. GTZ3196000R0001)
Triangular probe for floor measurements
per EN 1081,
DIN VDE 0100-600 (RE
(INS)
)
Test probe for remote triggering (material no. Z550A)
Optional plug-on measurement cable with a triggering
key on the test probe and an additional key for illumi-
nating the measuring point, including shielded, plug-in
connector cable
RS-232 Profiscanner for barcodes (material no. Z502F)
Barcode scanner for RS 232 connection (laser sen-
sor), variable barcode length, enhanced reading accu-
racy,
with coil cable
SCANBASE RFID (material no. Z751G)
RFID read/write for RS 232 port (13.56 MHz)
VARIO Plug Adapter Set (material no. Z500A)
Probe set (material no. Z503F)
Set of test probes (red/black)
CAT III 600 V, 1 A, test probe working range:
68 mm – diameter: 2.3 mm
TR25 reel (material no. GTZ3303000R0001)
Reel with 25 m measurement cable
TR50 drum (material no. GTY1040014E34)
Drum with 50 m measurement cable
PRO-PE clip (material no. Z503G)
Flat test clip for contacting busbars quickly and safely.
Good contact at the front and back of the busbar
thanks to time-tested contact blades. Rigid 4 mm
socket in the handle, suitable for the insertion of
spring-loaded 4 mm plugs with rigid insulating sleeve,
1000 V CAT IV/32 A.
Further accessories and additional information concerning accessories can be
found in the data sheet for the PROFITEST INTRO.
Test Standard Test Current
Open-Circuit
Voltage
R
SL
Housing –
Mains Plug
VDE 0701-0702:2008 > 200 mA 4 V < U
L
< 24 V
0.3 
1
+ 0.1
2
for each addi-
tional 7.5 m
Tes t
Standard
Tes t
Voltage
R
INS
PC I PC II PC III Heating
VDE 0701-
0702:2008
500 V 1 M 2M 0.25 M 0.3 M *
Test Standard
I
PE
I
C
I
DI
VDE 0701-0702:2008
PC I: 3.5
1 mA/kW *
0.5
PC I:
3.5
1 mA/
kW *
PC II:
0.5
Test Standard I
EL
VDE 0701-0702:2008
PC I: 3.5
1 mA/kW
1
PC II: 0.5

Table of Contents