DC Inverter Side Discharge VRF for North America
60
(2) Usage of converter configuring software:
When the converter is working, hold the button ”SETfor 5 sec. Function LED will be
flickering, indicating that the converter has enter the baud rate setting mode. Then
you can use the converter configuring software to set the baud rate of converter.
Baud rate supported by the converter (baud rate of air conditioner’s communication
interface matches with the baud rate of USB interface automatically):
Ex-factory defaulted baud rate: (unit: bps)
AC is connected with
Baud rate of air conditioner interface
Baud rate of USB interface
CAN
20000
/
50000
self-adaptive
115200
HBS
57600
38400
RS485
9600
9600
Baud rate look-up table for RS485 interface (unit: bps)
RS485 interface
4800
9600
19200
38400
57600
115200
USB interface
4800
9600
19200
38400
57600
115200
Baud rate look-up table for HBS interface (unit: bps)
HBS interface
9600
19200
38400
57600
USB interface
4800
9600
19200
38400
Baud rate look-up table of CAN interface (unit: bps)
Double-click the desktop shortcut.
CAN interface
20000
50000
100000
125000
USB interface
115200
115200
256000
256000