DC Inverter Side Discharge VRF for North America
73
5.3 Selection of Indoor Branches
Select indoor branches according to the total capacity of downstream indoor units. if
the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.
Refrigerant system
Total capacity of downstream indoor units C (Btu/h)
Model
Y type branch
C< 68200
FQ01A
68200C102400
FQ01B
102400C 238800
FQ02
238800C 460600
FQ03
460600C
FQ04
5.4 Dimension of Pipe between Indoor Branches
Select pipe between indoor branches according to the capacity of downstream indoor
units; if the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.