GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
327
3. BACnet Gateway Topology
As shown in the topological diagram below, the whole system consists of the internal network of the air
conditioning unit and BACnet/IP network through which the communication data can be exchanged.
In the network above, L3 is the line for RJ45 and L2 is the twisted pair line.
Note: the total length of L2 can not exceed 500 m and a matched resistance shall be added at both ends.
4. Hardware
4.1 BACnet Product Overview
BACnet gateway kits MG30-24/D2(B) are intended to realize the data exchange between the air
conditioning unit and BAS, and providing 8 I/Os (four inputs are E0, E1. E/A2, E/A3 and four outputs are
E/A4, E/A5, A6, A7). E0 is the fire alarm interface. The status of other I/Os is mapped to the specific
objects of the BACnet/IP bus and is defined by the user.