GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
150
2.2.4.18 b2 Defrost temperature sensor 1 error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting:
2.2.4.19 b3 Defrost temperature sensor 2 error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal