GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
158
Troubleshooting:
2.2.4.29 C3 main control and inverter fan drive communication error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If ODU hasnt received inverter fan drive board data in continuous 30s, report the error.
Possible reason
Communication wire between ODU mainboard inside module and inverter fan drive board is not
connected properly
Inverter fan drive board is abnormal
Mainboard is abnormal