GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
174
Error judgment condition and method:
Test compressor suction pressure through low pressure sensor. When pressure value is lower than
-41
°C
, the unit will stop for protection.
Possible reason:
Cut-off valve of ODU is not fully opened;
Low pressure sensor is abnormal;
Outdoor or indoor fan is not working properly;
IDU filter or air duct is blocked (cooling mode);
Ambient temperature is too low;
Refrigerant charging amount is insufficient;
System pipeline is blocked;