EasyManua.ls Logo

Gree GMV5 - Page 195

Gree GMV5
321 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GREE Photovoltaic Direct-driven Inverter Multi VRF Units
191
■Poor contact between air outlet temperature sensor and terminal in mainboard interface
■Air outlet temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting:
2.3.4.53 “db” Project debugging
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
This is a status code of project debugging, not a error code. When IDU or ODU displays this code, it
means the unit is under debugging status and the IDU cannot be operated.
Troubleshooting: ——
Possible reason
——
2.3.4.54 “E1” High pressure protection
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Judge through high pressure sensor detecting system real-time high pressure or action of high
pressure switch. If the sensor detects that high pressure is bigger than 65
or high pressure switch is
cut off, it is judged that high pressure is too high and the system stops operation for protection.
Possible reason:
■Cut-off valve of ODU is not fully opened;
■High pressure sensor is abnormal;
■High pressure switch is abnormal;
■Outdoor or indoor fan is not working properly;
■IDU filter or air duct is blocked (heating mode);
■Ambient temperature is too high;

Table of Contents

Related product manuals