EasyManua.ls Logo

Gree GRS-CQ8.0Pd/NaEK - Nominal Working Conditions; Operation Range; Electric Data

Gree GRS-CQ8.0Pd/NaEK
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product
9
Cooling
Indoor Water Temperature: 23°C/18°C; Outdoor Temperature: 35°CDB/24°CWB
Heating
Indoor Water Temperature: 30°C/35°C; Outdoor Temperature: 7°CDB/6°CWB
“*2” indicates the capacity and power input are tested based on the conditions below:
Cooling
Indoor Water Temperature: 12°C/7°C; Outdoor Temperature: 35°CDB/24°CWB
Heating
Indoor Water Temperature: 40°C/45°C; Outdoor Temperature: 7°CDB/6°CWB
1.5.2 Nominal Working Conditions
Item
Water Side
Air side
Entering Water Temp
(°C)
Leaving Water
Temperature (°C)
Dry Bulb
Temperature (°C)
Wet Bulb
Temperature (°C)
Floor Heating
30
35
7
6
FCU Heating
40
45
7
6
Floor Cooling
23
18
35
FCU Cooling
12
7
35
Water Heating
10
50
7
6
1.5.3 Operation Range
Item
Water Side
Air side
Leaving Water Temperature (°C)
Environment Dry Bulb Temperature (°C)
Cooling
7
25
10~48
Heating
25
55
-22~35
Water Heating
40~80 (Water Tank Temperature)
-22~45
Note: when operating conditions are out of the range listed above, please contact GREE.
1.5.4 Electric Data
Model
Power Supply
Leakage Switch
Minimum Sectional
Area of Earth Wire
Minimum Sectional
Area of Power
Supply Wire
V,Ph,Hz
(A)
(mm
2
)
(mm
2
)
GRS-CQ8.0Pd/NaE-K(O
)
220-240V,~,50Hz
25
3.3
2×3.3
GRS-CQ10Pd/NaE-K(O)
25
3.3
2×3.3
GRS-CQ8.0Pd/NaE-K(I)
50
13.3
2×13.3
GRS-CQ10Pd/NaE-K(I)
50
13.3
2×13.3
GRS-CQ12Pd/NaE-K(O)
35
8.4
2×8.4
GRS-CQ14Pd/NaE-K(O)
35
8.4
2×8.4
GRS-CQ16Pd/NaE-K(O)
35
8.4
2×8.4
GRS-CQ12Pd/NaE-K(I)
50
13.3
2×13.3
GRS-CQ14Pd/NaE-K(I)
50
13.3
2×13.3
GRS-CQ16Pd/NaE-K(I)
50
13.3
2×13.3
GRS-CQ12Pd/NaE-M(O)
380-415V,3N~,50Hz
25
3.3
4×3.3

Table of Contents