Page #55 background image
52
Installation and Maintenance
Service Manual
5. Diagnosis for compressor synchronism (AP1 below is control board of outdoor unit)
Main detection point:
● If the system pressure is over-high?
● If the work voltage is over-low?
Malfunction diagnosis process:
If the compressor wire COMP(UVW) is well
connected, the connection sequence
forwards to clockwise direction?
Check if the fan
terminal OFAN is
connected well
Replace
compressor
If the outdoor fan works
normally?
If the stop time of
compressor is more than
3min
Synchronism after
energize the unit
and start it
Connect
wire well
Synchronism
occurred during
operation
Replace
control board
AP1
If the radiating of unit is
well?
Remove
malfunction?
Improve the radiating
of unit (clean heat
exchanger and
increase ventilation)
Replace fan
capacitor C1
Replace
outdoor fan
Y
N
N
N
Y
Y
N
Replace
control board
AP1
Remove
malfunction?
Replace
compressor
Y
N
N
Y
If the input voltage of unit
is normal?
Start to run until the
power resume normal
voltage
N
If the refrigerant is too
much?
Charge the
refrigerant with
service manual
Y
Y
N
Y
End
End

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GWC24QE-D3DNA6E/I and is the answer not in the manual?

Gree GWC24QE-D3DNA6E/I Specifications

General IconGeneral
BrandGree
ModelGWC24QE-D3DNA6E/I
CategoryAir Conditioner
LanguageEnglish

Related product manuals