60
Service Manual
Installation and Maintenance
6. Diagnosis for compressor synchronism (AP1 below is control board of outdoor unit)
Main detection point:
● If the system pressure is over-high?
● If the work voltage is over-low?
Malfunction diagnosis process:
If the compressor wire COMP(UVW) is well
connected, the connection sequence
forwards to clockwise direction?
Check if the fan
terminal OFAN is
connected well
Replace
compressor
If the outdoor fan works
normally?
If the stop time of
compressor is more than
3min