Double-8 display
According to the different setting of remote control, the nixie light may display the current temperature (the temperature scope is
from 60.8 to 86
o
F) and indoor ambient temperature. The heating and air supply temperature will display 77
o
F under auto-mode, the
temperature will display 64.4
o
F under the heating mode, and the temperature will display H1 under the defrosting mode.(If you set
the fahrenheit temperature display, the nixie light will display according to fahrenheit temperature)
(11) Drying Function
You may start or stop the drying function under the modes of cooling and dehumidify at the starting status (The modes of automatism,
heating and air supply do not have drying function). When you start the drying function, after stop the machine by pressing the switch
button, you should keep running the inner fans for 10 minutes under low air damper (The swing will operate as the former status
within 10 minutes, and other load is stopped), then stop the entire machine; When you stop the drying function, press the switch
button will stop the machine directly. When you start the drying function, operating the drying button will stop the inner fans and close
the guide louver.
(12) Memory function when interrupting the power supply
Memory content: mode, swing function, light, set temperature and wind speed. After interrupted the power supply, the machine will
start when recovering the power according to the memory content automatically. If the last remote control command has not set
the timed function, the system will remember the last remote control command and operate according it. If the last remote control
command has set timed function and the power supply is interrupted before the timed time, the system will remember the timed
function of the last remote control command, the timed time will recounted form power on. If the last remote control command has
set timed function, the time is out and the system is start or stop according to the set time when the power supply is interrupted, the
system will remember the operation status before the power supply was interrupted, and do not carry out timed action; The timed
clock will not remembered.
(13)Control of Outdoor Electric Heating Band
If not in heating mode or temp sensor has malfunction, electric heating bands of compressor and of condenser will stop operation,
otherwise, the below control logic will be followed.
1. Control of Compressor Electric Heating Band
a. Conditions for startup: the compressor is off and meanwhile outdoor ambient temp ≤23
°F;
b. Conditions for turning off: it will be turned off when meeting any condition below:
Compressor is operating
Compressor is turned off and meanwhile the outdoor ambient temperature ≥28.
°F;
c. Outdoor ambient temp sensor has malfunction and electric heater band stops operation.
2. Control of electric heater band of condenser
ķWhen Toutdoor amb.≤33.8
°F, electric heater band of condenser will operate.
ĸDuring defrosting process, electric heater band of chassis will operate in 3min after compressor starts operating. When
compressor has operated for 3min and Toutdoor amb.≥37.4
°F, electric heater band will stop operating.
ĹWhen Toutdoor amb.≥37.4
°F, electric heater band of condenser will not operate.
ĺWhen 33.8
°F˘Toutdoor amb.˘37.4°F, electric heater band of condenser will keep its previous status.
When outdoor ambient temp sensor has malfunction, electric heater band stops operation; once electric heater stops operation, it
has to wait at least 2 min before it can be restarted up again.