EasyManua.ls Logo

Gree GWHD(28)NK3FO - Specifications

Gree GWHD(28)NK3FO
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
Technical Information
Service Manual
Model GWHD(18)NK3FO
Product Code CB228W03500/CB228W03501
Power
supply
Rated Voltage V~ 220-240V
Rated Frequency Hz 50
Phases 1
Cooling capacity(max~min) W 5000(2050~6200)
Heating capacity(max~min) W 5600(2500~6650)
Cooling Power Input(max~min) W 1550(500~2550)
Heating Power Input(max~min) W 1550(580~2700)
Cooling Current Input A 6.88
Heating Current Input A 6.88
Rated Power Input W 2700
Rated Current A 11.98
SEER W/W 5.6
SCOP W/W 3.8
Outdoor
Unit
Compressor Trademark ZHUHAI LANDA COMPRESSOR CO.,LTD
Compressor Model QXA-B141zF030A
Compressor Refrigerant Oil Type RB68EP
Compressor Type Rotary
L.R.A A /
Compressor Rated Load Amp (RLA) A 7.2
Compressor Power Input W 1440
Compressor Thermal Protector 1NT11L-6233
Throttling Method Electron expansion valve
Cooling Operation Ambient Temperature Range
O
C -15~48
Heating Operation Ambient Temperature Range
O
C -15~24
Condenser Material Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Φ7
Rows-Fin Gap(mm) mm 2-1.4
Coil length (l) X height (H) X coil width (L) mm 851X38.1X660
Fan Motor Speed (rpm) (H/M/L) rpm 630
Output of Fan Motor W 60
Fan Motor RLA A /
Fan Motor Capacitor μF /
Air Flow Volume of Outdoor Unit m
3
/h 3200
Fan Type-Piece Axial-ow
Fan Diameter mm Φ520
Defrosting Method Automatic Defrosting
Climate Type T1
Isolation I
Moisture Protection IP24
Permissible Excessive Operating Pressure for the
Discharge Side
MPa 4.3
Permissible Excessive Operating Pressure for the
Suction Side
MPa 2.5
Dimension (WXHXD) mm 963X700X396
Dimension of Package (LXWXH) mm 1026X455X735
Dimension of Package(LXWXH) mm 1029X458X750
Net Weight kg 50
Gross Weight kg 55
efrigerant Charge R410A
Refrigerant Charge kg 1.40
2. Specications

Related product manuals