79
Test Operation, Troubleshooting and Maintenance
Replacement of the compressor
Note: be sure there is no refrigerant inside the system and power supply has been cut off before
replacement.
Steps Image Instructions
4. Loosen screws
at feet of the
compressor.
Loosen screws at feet of the
compressor with a adjustable
or box spanner.
Loosened screws should be
put together to avoid loss.
5. Replace the
compressor with
a new one.
During replacement, care
must be taken to not damage
rubber pads.
Seal the replaced compressor
to prevent moisture entering;
Place a new compressor
at the rubber pads. Steel
bushing is required for rubber
pads.
Tighten the steel bushing with
screws.
6. Reconnect
the suction line,
the discharge
line, other pipes
and electric
lines. Then,
check for normal
operation of the
compressor.
Reconnect and resolder the
suction and discharge lines.
Do charge nitrogen during
soldering.
After soldering, charge high-
pressure nitrogen for the leak
test.
Power on the unit and start it
through a AC contact for 2~3
seconds.
When the compressor runs
reversely, it would generate
harsh noise.

Table of Contents