AIR-TO-WATER HEAT PUMP CONTROL
12
UNITS CONTROL
1 OPERATION FLOWCHART
2 MAIN LOGIC
2.1 Defrosting Mode
2.1.1 The condition of start defrosting mode:
Under heating mode or water heating mode, if the accumulative running time of
compressor is over the set interval time of defrostingdefault 50minand the defrosting
temperature(outdoor unit heat exchanger temperature) is lower than the set starting
temperature(default -4) ,the unit will start running defrosting, and the 4-way valve will
shut off and the outdoor fan will stop