AIR-TO-WATER HEAT PUMP INSTALLATION
82
Pipe size
(Diameter:Φ)
Length B Elevation A
model
gas Liquid Standard Max. Standard Max.
Additional
refrigerant
GRS-CQ6.0Pd/Na-K
1/2" 1/4"
5.0m 20m 0m 10m 20g/m
GRS-CQ8.0Pd/Na-K
5/8" 3/8"
7.5m 30m 0m 15m 50g/m
GRS-CQ10Pd/Na-K
5/8" 3/8"
7.5m 30m 0m 15m 50g/m
GRS-CQ12Pd/Na-K
5/8" 3/8"
7.5m 30m 0m 15m 50g/m
GRS-CQ14Pd/Na-K
5/8" 3/8"
7.5m 30m 0m 15m 50g/m
GRS-CQ16Pd/Na-K
5/8" 3/8"
7.5m 30m 0m 15m 50g/m
GRS-CQ12Pd/Na-M
5/8" 3/8"
7.5m 30m 0m 15m 50g/m
GRS-CQ14Pd/Na-M
5/8" 3/8"
7.5m 30m 0m 15m 50g/m
GRS-CQ16Pd/Na-M
5/8" 3/8"
7.5m 30m 0m 15m 50g/m

Related product manuals