A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
182
system and that the power has been cut off.
Step Illustration Handling Instruction
1.拆除电磁阀
A. 先切断电源。
B. 妥善回收冷媒
C. 用扳手松掉固定
电磁阀螺栓
2.移开电磁阀
将电磁阀从四通阀上
取下,移开。
3. Remove the
4-way valve
Use gas welding to
heat the pipes
connected on the four
opennings of 4-way
valve. Then, pull them
out from 4-way valve.
Before welding 4-way
valve, please record the
orientation of 4-way
valve and installing
position of each
opening.
4. Remove 4-way
valve
Remove the old 4-way
valve from the unit.