25
Air to Water Heat Pump
Service Manual- Versati II Series
CONTROL
[Notes]
①
When “Floor debug” or “Emergen� Mode” is activated, then the control will not receive signals from the
thermostat.
②
If “Thermostat” is set to “On”, the control will automatically disable some functions concerning timer, and
run in accordance with the mode set by the thermostat. In this case, the running mode is unchangeable and the
ON/OFF key operation of the control is ineffective.
③
When this setting is saved successfully, it will be memorized upon power failure.
④
The state of the Thermostat can be changed when the unit is turned off.
3�3�2�19 IDU Heater
Go to the FUNCTION page and locate “IDU Heater”, then, congure it through the Up/Down key, “With” or
“Without”.
[Notes]
it will be memorized upon power failure.
3�3�2�20 Other Heater
Go to the FUNCTION page and locate Other heater, then, congure it through the Up/Down key, “With” or
“Without”.
[Notes]
it will be memorized upon power failure.
3�3�2�21 Underpan Heater
Go to the FUNCTION page and locate “Underpan Heater” then, congure it through the Up/Down key, “With”
or “Without”.
[Notes]
it will be memorized upon power failure.
3�3�2�22 Water Tank
Go to the FUNCTION page and locate “Water tank” then, congure it through the Up/Down key, “With” or
“Without”.
[Notes]
①
It will be memorized upon power failure.
②
This setting is allowed only when the unit is turned off.
3�3�2�23 Tank Sensor
Go to the FUNCTION page and locate “Water tank”, then, congure it through the Up/Down key, “1” or “2”.
When the water tank is unavailable, this option will be reserved.
[Notes]
it will be memorized upon power failure.
3�3�2�24 Solar Heater
Go to the FUNCTION page and locate “Solar heater”, then, congure it through the Up/Down key, “With” or
“Without”.
[Notes]
it will be memorized upon power failure.
3�3�2�25 FCU
Go to the FUNCTION page and locate “FCU”, then, configure it through the Up/Down key, “With” or
“Without”.
[Notes]
It will be memorized upon power failure.
3�3�2�26 Remote Sensor
Go to the FUNCTION page and locate “Remote sensor”, then, congure it through the Up/Down key, “With”
or “Without”.
[Notes]
It will be memorized upon power failure.
“T-room ctrl” can be selected only when the Remote Sensor is set to “With”.
3�3�2�27 Air removal
Go to the FUNCTION page and locate “Air removal”, then, congure it through the Up/Down key, “On” or
“Off”.
[Notes]
①
It will not be memorized upon power failure.
②
It can be set only when the unit is turned off.