7
Air to Water Heat Pump
Service Manual- Versati Series
QSPEVDU
4.1.2 Indoor Unit
INDOOR UNIT
Model
GRS-
CQ6.0Pd/
Na-K(I)
GRS-
CQ8.0Pd/
Na-K(I)
GRS-
CQ10Pd/
Na-K(I)
GRS-
CQ12Pd/
Na-K(I)
GRS-
CQ14Pd/
Na-K(I)
Product Code
ER010N1050 ER010N1040 ER010N1000 ER010N1020 ER010N1030
Power Supply
V,Ph,Hz
220-240V,~,50Hz
Rated input (indoor only) W 3200 6200
Liquid side diameter
mm
(inch)
6.35(1/4) 9.52(3/8)
Gas side diameter
mm
(inch)
12.7(1/2) 15.9(5/8)
2SHUDWLRQ5DQJH2XWÀRZ
water temp.)
Cooling (FCU) 7-25
Cooling (Floor ) 18-25
Heating (FCU) 25-55(High Temperature Cycle)
Heating (Floor ) 25-45 (Low Temperature Cycle)
Main
components
pump
Type - Water-cooled
Nr. of speed - 3
Power input W 200
:DWHUÀRZ
limit
LPM 12
Expansion
Vessel
Volume Liter 10
Water Pressure
(Max)
Bar 3
Water Pressure
(Pre)
Bar 1
Electric
Heater
Type - Sheath
Material - Stainless Steel
Operation - Automatic
Steps - 2
Capacity
Combination
KW 1.5+1.5 3+3
Power input
V,Ph,Hz
230V,~,50Hz
Heat
Exchanger
Type - Brazed Plate HEX
Quantity - 1
Outline Dimension (W×D× H) mm 900×500×324
Net Weight kg 52 52 52 53 53