Air to Water Heat Pump
Service Manual- Versati Series
QSPEVDU
4.3 Electrical Data
Model
Power Supply Leakage Switch
Minimum Sectional
Area of Earth Wire
Minimum Sectional Area
of Power Supply Wire
V,Ph,Hz (A) (mm
2
) (mm
2
)
GRS-CQ6.0Pd/Na-K(I)
220-240V,~,50Hz
32 4 3×4
GRS-CQ8.0Pd/Na-K(I) 50 10 3×10
GRS-CQ10Pd/Na-K(I) 50 10 3×10
GRS-CQ12Pd/Na-K(I) 50 10 3×10
GRS-CQ14Pd/Na-K(I) 50 10 3×10
GRS-CQ16Pd/Na-K(I) 50 10 3×10
GRS-CQ6.0Pd/Na-K(O) 32 4 3×4
GRS-CQ8.0Pd/Na-K(O) 32 4 3×4
GRS-CQ10Pd/Na-K(O) 32 4 3×4
GRS-CQ12Pd/Na-K(O) 40 6 3×6
GRS-CQ14Pd/Na-K(O) 40 6 3×6
GRS-CQ16Pd/Na-K(O) 40 6 3×6
GRS-CQ12Pd/Na-M(I)
380-415V,3N~,50Hz
16 1.5 5×1.5
GRS-CQ14Pd/Na-M(I) 16 1.5 5×1.5
GRS-CQ16Pd/Na-M(I) 16 1.5 5×1.5
GRS-CQ12Pd/Na-M(O) 25 2.5 5×2.5
GRS-CQ14Pd/Na-M(O) 25 2.5 5×2.5
GRS-CQ16Pd/Na-M(O) 25 2.5 5×2.5
GRS-CQ16Pd/Na-H(I)
380V,3N~,60Hz
16 1.5 5×1.5
GRS-CQ16Pd/Na-H(O) 25 2.5 5×2.5
Note:
ķ
Leakage Switch is necessary for additional installation. If circuit breakers with leakage protection are in
use, action response time must be less than 0.1 second, leakage circuit must be 30mA.
ĸ
The above selected power cable diameters are determined based on assumption of distance from the
distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m to 150m, diameter of
power cable must be increased to a further grade.
Ĺ
The power supply must be of rated voltage of the unit and special electrical line for air-conditioning.
ĺ
All electrical installation shall be carried out by professional technicians in accordance with the local
laws and regulations.
Ļ
Ensure safe grounding and the grounding wire shall be connected with the special grounding equipment
of the building and must be installed by professional technicians.
ļ
7KHVSHFL¿FDWLRQVRIWKHEUHDNHUDQGSRZHUFDEOHOLVWHGLQWKHWDEOHDERYHDUHGHWHUPLQHGEDVHGRQ
the maximum power (maximum amps) of the unit.
Ľ
7KHVSHFL¿FDWLRQVRIWKHSRZHUFDEOHOLVWHGLQWKHWDEOHDERYHDUHDSSOLHGWRWKHFRQGXLWJXDUGHGPXOWL
wire copper cable (like, YJV XLPE insulated power cable) used at 40
ć
and resistible to 90
ć
(see IEC 60364-5-
,IWKHZRUNLQJFRQGLWLRQFKDQJHVWKH\VKRXOGEHPRGL¿HGDFFRUGLQJWRWKHUHODWHGQDWLRQDOVWDQGDUG
ľ
7KHVSHFL¿FDWLRQVRIWKHEUHDNHUOLVWHGLQWKHWDEOHDERYHDUHDSSOLHGWRWKHEUHDNHUZLWKWKHZRUNLQJ
temperature at 40
ć
,IWKHZRUNLQJFRQGLWLRQFKDQJHVWKH\VKRXOGEHPRGL¿HGDFFRUGLQJWRWKHUHODWHGQDWLRQDO
standard.

Related product manuals