Gree Vireo B 9 MBH - IDU Fan Motor Malfunction

Gree Vireo B 9 MBH
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48
Installation and Maintenance
Service Manual
2.
Malfunction of Blocked Protection of IDU Fan Motor H6
Measure the voltage of this foot to neutral
wire on the mainboard
Start
off stir the blade with a tool
While power is
smoothly
Repl ace PG m otor
End
yes
no
Is malfunction
eli m inated
yes
no
Insert the control
ter m inal of PG
motor tightly
no
no
Rei nstall the blade and
motor correctly
Is malfunction
eli m inated
no
no
yes
yes
Tur n on the
unit again ; measure whether the output
voltage on control ter m inal for PG motor
is more than 50V within 1 min after the
louvers ar e opened
no
yes
yes
Is the motor
started up
no
Is m alfunction
eliminated
yes
yes
yesno
yes
Is m alfunction
eli m inated
Tighten the screw; reassemble the blade, motor
and shaft bearing rubber base sub-assy to make
sure there is no foreign object between them
Replace the mainboard
with the same model.
Check if the connection of PG
motor feedback terminal is firm.
Check if the connection
of PG motor control
terminal is firm.
to see whether the blade rotates