AUTOCALL®
TFX-500Mj800M System Overview,
Control
Panel Assembly, Start-Up
Publication Number 19700367
Issue 3, January, 1997
Read and understand
all
instructions before proceeding.
The
Autocall TFX-500M and TFX-800M fire protection systems are
microprocessor
based and use a mix
of
new
and traditional
technology. They are versatile, flexible, and completely suitable for
application in small to medium sized premises or systems.
---------
---
---
-------
=1='=
=:=
=1=
= =
:!
:i=
:1
:'
:.
: : :
---------
TFX-500M-
The Autocall TFX-500M
is
field programmable to
allow for up to 198 individual detection or annunciation points.
Device
pOints can be organized into 16 conventional zones and
up
to 240 control-by-event groups.
Two 2-way data circuits (multiplex) provide communication to and
from a variety
of
input and output devices. Conventional (non-ad-
dressable) detectors may
be
connected, individually or
in
small
groups, to the data circuits using the IXA-500DM or IXA-500DMA
Conventional Detector Modules. The TFX-500 also connects to
off-site central stations and municipal fire alarm circuits.
TFX-800M-
The Autocall TFX-800M expands the capacity of the
Autocall TFX-500 to allow
up
to 990 individual points, 80 zones, and
ten 2-way data (multiplex) circuits.
Standard Features
Modular and Scalable Packaging
Allows TFX to be sized to specific system requirements
"Dead front," with locked access to operator control panel
functions and additional locked access to electronics
Fits standard Autocall backboxes, and uses Autocall 19- by
5.25-inch module
format
Front Door Operator
Controls-Fire
Control Module,
Operator
Display Module, 16 Indicator Module, 80 Indicator
Module, 40 x 2 Indicator Module, 16 Status control Module,
40 Status
Control Module.
Status Control Modules may
be
used for fan control,
damper control, speaker control, zone disconnect switches,
fire phone control, general purpose switches.
Programmability
Zone identification and point messages
Operator passcode levels
Point to zone assignment
General or selective alarm signalling
Alert or Evacuation signalling
Non-silenceable waterflow alarms
I/O control-by-event functions grouping
Automatic and manual detector sensitivity adjustment
Bell mapping--defines the way the signalling appliance
respond to Alert or Evacuation signal
e Test reminder--disp!ays a warning message
and
sends an
audible alert when the routine, weekly test
is
due.
Capacity
TFX-500M-198
addressable devices,
on
two 2-way data
ioops (multipiex communications)-99
I/O devices per loop.
TFX-800M-990
addressable devices,
on
ten 2-way data
100ps-99
I/O devices per loop.
Two common alarm annunciation circuits (1.0
Amp
max per
circuit).
Functions
Ground Fault detection
Waterflow Alarm
Fire Drill
Supervisory Condition Indication
Loop Fault
1/0 Isolation (disabling) and De-Isolation (enabling)
Alarm
Silence
System
Reset
Device functional testing
Solo Test
Alarm Verification
Manual operation
of
common alarm and fault relays
Optional Features
Offsite signalling with City Box Transmitter
Module--CEB-500
(PIN 940524), Reverse Polarity
Transmitter Module--CVB-500 (PIN 940525), Digital Alarm
Communicator Transmitter Interface Module-SRA-550
(P/N 940572).
Auxiliary Relay
Module-ARM-500
(PIN 9760130) provides
eight relay outputs.
Expansion InpuVOutput Modules
(XIOMs)-IM-16
Input
Module (PIN 976067) and
OM-i6
Output Module (PIN
976066)-provide
inpuVoutput communication functions
such as driving digital display outputs and accepting digital
inputs from volt-free contacts.
Two Printer
Options-Autocall
Printer option
(PIN
976018 or
976264)-piOvides
a permanent printed record
of
system
activity.
TFXnet Communications
System-Up
to 62 TFX-500/800
fire panels connect to a single TFXnet network (supports up
to
59,400 analog/addressable points; 4800 zones). RS-485,
fiber optic, and dedicated telephone wire communications
between network nodes is supported.
AUTOCALL TFX-500M and TFX-800M Operator's Manual and Installation Guide
Page
1
firealarmresources.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grinnell AUTOCALL TFX-500M and is the answer not in the manual?

Grinnell AUTOCALL TFX-500M Specifications

General IconGeneral
BrandGrinnell
ModelAUTOCALL TFX-500M
CategoryControl Panel
LanguageEnglish