AUTOCALL®
TFX-500Mj800M System Overview,
Control
Panel Assembly, Start-Up
Publication Number 19700367
Issue 3, January, 1997
Read and understand
all
instructions before proceeding.
The
Autocall TFX-500M and TFX-800M fire protection systems are
microprocessor
based and use a mix
of
new
and traditional
technology. They are versatile, flexible, and completely suitable for
application in small to medium sized premises or systems.
---------
---
---
-------
=1='=
=:=
=1=
= =
:!
:i=
:1
:'
:.
: : :
---------
TFX-500M-
The Autocall TFX-500M
is
field programmable to
allow for up to 198 individual detection or annunciation points.
Device
pOints can be organized into 16 conventional zones and
up
to 240 control-by-event groups.
Two 2-way data circuits (multiplex) provide communication to and
from a variety
of
input and output devices. Conventional (non-ad-
dressable) detectors may
be
connected, individually or
in
small
groups, to the data circuits using the IXA-500DM or IXA-500DMA
Conventional Detector Modules. The TFX-500 also connects to
off-site central stations and municipal fire alarm circuits.
TFX-800M-
The Autocall TFX-800M expands the capacity of the
Autocall TFX-500 to allow
up
to 990 individual points, 80 zones, and
ten 2-way data (multiplex) circuits.
Standard Features
Modular and Scalable Packaging
• Allows TFX to be sized to specific system requirements
• "Dead front," with locked access to operator control panel
functions and additional locked access to electronics
• Fits standard Autocall backboxes, and uses Autocall 19- by
5.25-inch module
format
• Front Door Operator
Controls-Fire
Control Module,
Operator
Display Module, 16 Indicator Module, 80 Indicator
Module, 40 x 2 Indicator Module, 16 Status control Module,
40 Status
Control Module.
• Status Control Modules may
be
used for fan control,
damper control, speaker control, zone disconnect switches,
fire phone control, general purpose switches.
Programmability
• Zone identification and point messages
• Operator passcode levels
• Point to zone assignment
• General or selective alarm signalling
•
Alert or Evacuation signalling
•
Non-silenceable waterflow alarms
• I/O control-by-event functions grouping
• Automatic and manual detector sensitivity adjustment
• Bell mapping--defines the way the signalling appliance
respond to Alert or Evacuation signal
e Test reminder--disp!ays a warning message
and
sends an
audible alert when the routine, weekly test
is
due.
Capacity
•
TFX-500M-198
addressable devices,
on
two 2-way data
ioops (multipiex communications)-99
I/O devices per loop.
•
TFX-800M-990
addressable devices,
on
ten 2-way data
100ps-99
I/O devices per loop.
• Two common alarm annunciation circuits (1.0
Amp
max per
circuit).
Functions
• Ground Fault detection
• Waterflow Alarm
• Fire Drill
•
•
•
•
•
Supervisory Condition Indication
Loop Fault
1/0 Isolation (disabling) and De-Isolation (enabling)
Alarm
Silence
System
Reset
• Device functional testing
• Solo Test
• Alarm Verification
• Manual operation
of
common alarm and fault relays
Optional Features
• Offsite signalling with City Box Transmitter
Module--CEB-500
(PIN 940524), Reverse Polarity
Transmitter Module--CVB-500 (PIN 940525), Digital Alarm
Communicator Transmitter Interface Module-SRA-550
(P/N 940572).
• Auxiliary Relay
Module-ARM-500
(PIN 9760130) provides
eight relay outputs.
• Expansion InpuVOutput Modules
(XIOMs)-IM-16
Input
Module (PIN 976067) and
OM-i6
Output Module (PIN
976066)-provide
inpuVoutput communication functions
such as driving digital display outputs and accepting digital
inputs from volt-free contacts.
• Two Printer
Options-Autocall
Printer option
(PIN
976018 or
976264)-piOvides
a permanent printed record
of
system
activity.
• TFXnet Communications
System-Up
to 62 TFX-500/800
fire panels connect to a single TFXnet network (supports up
to
59,400 analog/addressable points; 4800 zones). RS-485,
fiber optic, and dedicated telephone wire communications
between network nodes is supported.
AUTOCALL TFX-500M and TFX-800M Operator's Manual and Installation Guide
Page