English (GB)
20
00102
RelayControl
Bit 0: SetCustomRelay
Bool
Control bit that sets the value of the custom relay.
0 = Relay state logical 0
1 = Relay state logical 1.
CustomRelayPulse
Bit 1: PulseRelay
Bool
Control bit that pulses the custom relay. 0 (no pulse) will be the resulting
state.
0 = No pulse
1 = Pulse.
00103 PitPump1Control Enum
Remote manual control of pump 1.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00104 PitPump2Control Enum
Remote manual control of pump 2.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00105 PitPump3Control Enum
Remote manual control of pump 3.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00106 PitPump4Control Enum
Remote manual control of pump 4.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00107 PitPump5Control Enum
Remote manual control of pump 5.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00108 PitPump6Control Enum
Remote manual control of pump 6.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00109 ScadaPinCode Unscaled
PIN code for SCADA systems, etc.
If PitStatus.ScadaPinCodeEnabled (register 00202, bit 4) is enabled, the
correct PIN code must be set in this register in order to gain access to
remote control and configuration.
Verify acceptance in PitStatus.WriteAccess (register 00202, bit 5).
00110 SetEventLogClearID Unscaled Selects which records to clear in the event log.
00111 SetInterlockTimeout 1 minute
Interlock timeout value measured in minutes.
Status of this register is read in InterlockTimeout (register 00226).
00112 SetRealTimeClockHI
1 second
Setting the real-time clock in the CU 36X in seconds since midnight January
1st 1970 (UNIX time).
First set SetRealTimeClockHI, then SetRealTimeClockLO in order to set a
new time in UNIX format.
00113 SetRealTimeClockLO
00114 SetRtcSecond 1 second Real-time clock: Second of the minute [0; 59].
00115 SetRtcMinute 1 minute Real-time clock: Minute of the hour [0; 59].
00116 SetRtcHour 1 hour Real-time clock: Hour of the day [0; 23].
00117 SetRtcDay 1 day Real-time clock: Day of the month [1; 31].
00118 SetRtcMonth 1 month Real-time clock: Month of the year [1; 12].
00119 SetRtcYear 1 year Real-time clock: Year [0; 254] = [year 2000; year 2254].
00120
SetRtc
Bit0: SetRtc
Bool
Control bit that sets the new real-time clock in the CU 36X.
1 = Set new real-time clock from the registers 00114 to 00119.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section 9.2 CIM configuration register block, address 00005, for
acknowledgement behaviour.
00121 SetOverflowLevel 0.01 m Setting a new level for activation of overflow level alarm.*
00122 SetHighLevel 0.01 m Setting a new level for activation of high-level alarm.*
00123 SetAlarmLevel 0.01 m Setting a new level for activation of alarm level alarm.*
00124 SetDryRunningLevel 0.01 m Setting a new level for activation of dry-running alarm.*
00125 SetFoamDrainingLevel 0.01 m Setting a new level for foam-draining stop.*
00126 SetStartLevelPump1 0.01 m Setting a new start level, pump 1.*
00127 SetStopLevelPump1 0.01 m Setting a new stop level, pump 1.*
00128 SetStartLevelPump2 0.01 m Setting a new start level, pump 2.*
00129 SetStopLevelPump2 0.01 m Setting a new stop level, pump 2.*
00130 SetStartLevelPump3 0.01 m Setting a new start level, pump 3.*
00131 SetStopLevelPump3 0.01 m Setting a new stop level, pump 3.*
Address Register name Scale Description