English (GB)
21
00132 SetStartLevelPump4 0.01 m Setting a new start level, pump 4.*
00133 SetStopLevelPump4 0.01 m Setting a new stop level, pump 4.*
00134 SetStartLevelPump5 0.01 m Setting a new start level, pump 5.*
00135 SetStopLevelPump5 0.01 m Setting a new stop level, pump 5.*
00136 SetStartLevelPump6 0.01 m Setting a new start level, pump 6.*
00137 SetStopLevelPump6 0.01 m Setting a new stop level, pump 6.*
00138 SetCurrentMaxAlarmGrp1 0.01 A Set current max. alarm for group 1*
00139 SetCurrentMinAlarmGrp1 0.01 A Set current min. alarm for group 1*
00140 SetCurrentMaxWarnGrp1 0.01 A Set current max. warning for group 1*
00141 SetCurrentMinWantGrp1 0.01 A Set current min. warning for group 1*
00142 SetCurrentMaxAlarmGrp2 0.01 A Set current max. alarm for group 2*
00143 SetCurrentMinAlarmGrp2 0.01 A Set current min. alarm for group 2*
00144 SetCurrentMaxWarnGrp2 0.01 A Set current max. warning for group 2*
00145 SetCurrentMinWantGrp2 0.01 A Set current min. warning for group 2*
00146 SetSetpointPump1 0.1 % Set PID control loop setpoint for pump 1*
00147 SetSetpointPump2 0.1 % Set PID control loop setpoint for pump 2*
00148 SetSetpointPump3 0.1 % Set PID control loop setpoint for pump 3*
00149 SetSetpointPump4 0.1 % Set PID control loop setpoint for pump 4*
00150 SetSetpointPump5 0.1 % Set PID control loop setpoint for pump 5*
00151 SetSetpointPump6 0.1 % Set PID control loop setpoint for pump 6*
00152 SetControlModePump1 enum
Set control mode for pump 1:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00153 SetControlModePump2 enum
Set control mode for pump 2:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00154 SetControlModePump3 enum
Set control mode for pump 3:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00155 SetControlModePump4 enum
Set control mode for pump 4:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00156 SetControlModePump5 enum
Set control mode for pump 5:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00157 SetControlModePump6 enum
Set control mode for pump 6:
0 = Fixed Frequency
1 = Linear Control
2 = Minimum Control
3 = PID control*
00158 SetFeedbackSensorTypePump1 enum
Sets the feedback sensor type for pump 1:
4 = Flow rate
5 = Level, pressure
6 = Level, Ultrasound
13 = User defined Sensor 1
14 = User defined sensor 2
15 = User defined sensor 3*
00159 SetFeedbackSensorTypePump2 enum
Sets the feedback sensor type for pump 2:
4 = Flow rate
5 = Level, pressure
6 = Level, Ultrasound
13 = User defined Sensor 1
14 = User defined sensor 2
15 = User defined sensor 3*
Address Register name Scale Description