English (GB)
25
00202
PitStatus
Bit 0: RESERVED
--
PitStatus
Bit 1: AlarmActive
Bool
Alarm condition.
0 = No active alarms
1 = One or more active alarms.
PitStatus
Bit 2: WarningActive
Bool
Warning condition.
0 = No active warnings
1 = One or more active warnings.
PitStatus
Bit 3: ManualControl
Bool
Manual control condition.
0 = No manual control
1 = Manual control.
PitStatus
Bit 4: ScadaPinCodeEnabled
Bool
PIN code functionality.
0 = No PIN code required
1 = PIN code required to perform remote control and configuration.
PitStatus
Bit 5: WriteAccess
Bool
Remote write access.
0 = No write access (PIN code is incorrect)
1 = Full write access (PIN code is either correct or not enabled).
00203 OperatingMode enum
Register for reading the actual operating mode of the pit.
0 = Standby (stopped from level control)
1 = Startup delay
2 = Pumping
3 = Stop delay
4 = Pumping max.
5 = Stopped
6 = Foam-draining
7 = Daily emptying
8 = Pump anti-seizing
9 = Manual control (all enabled pumps in manual control mode)
10 = Interlock control (the pit is interlocked)
11 = Mains supply fault
12 = Level sensor fault
13 = All enabled pumps in alarm
14 = All pumps out of operation
15 = CU 36X controller in service mode
00204
PitPumpsPresence
Bit 0: Pump1Presence
Bool
Presence of pump 1.
0 = Not present
1 = Present.
PitPumpsPresence
Bit 1: Pump2Presence
Bool
Presence of pump 2.
0 = Not present
1 = Present.
PitPumpsPresence
Bit 2: Pump3Presence
Bool
Presence of pump 3.
0 = Not present
1 = Present.
PitPumpsPresence
Bit 3: Pump4Presence
Bool
Presence of pump 4.
0 = Not present
1 = Present.
PitPumpsPresence
Bit 4: Pump5Presence
Bool
Presence of pump 5.
0 = Not present
1 = Present.
PitPumpsPresence
Bit 5: Pump6Presence
Bool
Presence of pump 6.
0 = Not present
1 = Present.
PitPumpsPresence
Bit 6: Mixer
Bool
Presence of mixer
0 = Not present
1 = Present.
Address Register name Scale Description