9.8 Pump 1 register block
All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name Scale Description
00401
Pump1Status
Bit 0: Presence
Bool
Presence of pump.
0 = Not present
1 = Present.
Pump1Status
Bit 1: Running
Bool
Running state of pump.
0 = Not running
1 = Running.
Pump1Status
Bit 2: MonitoringFault
Bool
Fault state of pump monitoring devices.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
Pump1Status
Bit 3: Warning
Bool
Warning state of pump.
0 = No warning
1 = Warning.
Pump1Status
Bit 4: Alarm
Bool
Alarm state of pump.
0 = No alarm
1 = Alarm.
Pump1Status
Bit 5: IO111Present
Bool
Presence of auxiliary equipment IO 111.
0 = Not present
1 = Present.
Pump1Status
Bit 6: IO111Fault
Bool
Fault state of auxiliary equipment IO 111.
0 = No fault
1 = Fault.
Pump1Status
Bit 7: MP204Present
Bool
Presence of auxiliary equipment MP 204.
0 = Not present
1 = Present.
Pump1Status
Bit 8: MP204Fault
Bool
Fault state of auxiliary equipment MP 204.
0 = No fault
1 = Fault.
Pump1Status
Bit 9: CUEPresent
Bool
Presence of auxiliary equipment CUE.
0 = Not present
1 = Present.
Pump1Status
Bit 10: CUEFault
Bool
Fault state of auxiliary equipment CUE.
0 = No fault
1 = Fault.
Pump1Status
Bit 11: PumpDisabled
Bool
Enabled/disabled state of pump.
0 = Enabled
1 = Disabled (e.g. for temporary maintenance).
00402 Pump1ControlSource enum
Control source of pump.
0 = Auto
1 = Switch
2 = Display
3 = Remote-controlled by bus.
00403 Pump1ConnectionType enum
Pump connection type.
0 = The pump is controlled from the CU 36X output relay.
1 = The pump is controlled from the IO 351B output relay.
2 = The pump is controlled from the CU 36X and VFD.
3 = The pump is controlled from the IO 351B and VFD.
00404 Pump1OperatingTimeHI
1 minute Total operating time.
00405 Pump1OperatingTimeLO
00406 Pump1TimeToServiceHI
1 minute Time to next service.
00407 Pump1TimeToServiceLO
00408 Pump1OperatingTimeYesterday 1 minute Operating time yesterday.
00409 Pump1OperatingTimeToday 1 minute Operating time today.
00410 Pump1LatestOperatingTime 1 second Operating time last time it was operated.
00411 Pump1StartCounterHI
Unscaled Total number of pump starts.
00412 Pump1StartCounterLO
00413 Pump1StartCounterYesterday Unscaled Total number of pump starts yesterday.
00414 Pump1StartCounterToday Unscaled Total number of pump starts today.
00415 Pump1StartsPerHour Unscaled Number of pump starts within the last hour.
00416 Pump1Flow 0.1 litre/s Calculated average or measured pump flow.
00417 Pump1LatestFlow 0.1 litre/s Latest calculated/measured flow (capacity).