00418 Pump1Current 0.1 A Motor current.
00419 Pump1LatestCurrent 0.1 A Latest motor current.
00420 Pump1Voltage 0.1 V Voltage.
00421 Pump1Insulation 10 kΩ Motor insulation resistance.
00422 Pump1WaterInOil 0.1 % Motor water-in-oil measurement.
00423 Pump1Alarms1 Bits See section 11.13 Alarms and warnings
00424 Pump1Alarms2 Bits See section 11.13 Alarms and warnings
00425 Pump1Alarms3 Bits See section 11.13 Alarms and warnings
00426 Pump1Warnings1 Bits See section 11.13 Alarms and warnings
00427 Pump1Warnings2 Bits See section 11.13 Alarms and warnings
00428 Pump1Warnings3 Bits See section 11.13 Alarms and warnings
00429 Pump1MotorTemperature1 1 °C Motor temperature 1.
00430 Pump1MotorTemperature2 1 °C Motor temperature 2.
00431 Pump1PowerHI
1 W Power consumption.
00432 Pump1PowerLO
00433 Pump1EnergyHI
0.1 kWh Energy consumption.
00434 Pump1EnergyLO
00435 Pump1CosPhi 0.01 Motor cos φ.
00436 Pump1Frequency 0.1 Hz Motor-applied frequency.
00437 Pump1VFDmode enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00438 Pump1Torque 0.1 Nm Motor torque.
00439 Pump1iAsym 0.1 % Line current asymmetry.
00440
Pump1Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump1Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00441 Pump1Alarms4 Bits See section 11.13 Alarms and warnings
00442 Pump1Warnings4 Bits See section 11.13 Alarms and warnings
00443 Pump1AntiBlockingCounter Bits Number of anti blockings in the pump
00444 Pump1AISetpointSelect enum
Analog input used as setpoint for pump 1:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00445 Pump1SetpointType enum
Setpoint type for pump 1:
0 = Fixed value
1 = Analog input
00446 Pump1FeedbackSensorType enum
Feedback sensor type for pump 1:
4 = Flow rate
5 = Level, pressure
6 = Level, Ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00447 Pump1ControlMode enum
Control mode for pump 1:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00448 Pump1ActualSetpoint 1 % Actual setpoint for pump 1
00449 Pump1FixedFrequency 0.01 Hz Fixed frequency for pump 1
Address Register name Scale Description