English (GB)
37
00468 Pump2Current 0.1 A Motor current.
00469 Pump2LatestCurrent 0.1 A Latest motor current.
00470 Pump2Voltage 0.1 V Voltage.
00471 Pump2Insulation 10 kΩ Motor insulation resistance.
00472 Pump2WaterInOil 0.1 % Motor water-in-oil measurement.
00473 Pump2Alarms1 Bits See section 11.13 Alarms and warnings
00474 Pump2Alarms2 Bits See section 11.13 Alarms and warnings
00475 Pump2Alarms3 Bits See section 11.13 Alarms and warnings
00476 Pump2Warnings1 Bits See section 11.13 Alarms and warnings
00477 Pump2Warnings2 Bits See section 11.13 Alarms and warnings
00478 Pump2Warnings3 Bits See section 11.13 Alarms and warnings
00479 Pump2MotorTemperature1 1 °C Motor temperature 1.
00480 Pump2MotorTemperature2 1 °C Motor temperature 2.
00481 Pump2PowerHI
1 W Power consumption.
00482 Pump2PowerLO
00483 Pump2EnergyHI
0.1 kWh Energy consumption.
00484 Pump2EnergyLO
00485 Pump2CosPhi 0.01 Motor cos φ.
00486 Pump2Frequency 0.1 Hz Motor-applied frequency.
00487 Pump2VFDmode enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00488 Pump2Torque 0.1 Nm Motor torque.
00489 Pump2Asym 0.1 % Line current asymmetry.
00490
Pump2Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump2Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00491 Pump2Alarms4 Bits See section 11.13 Alarms and warnings
00492 Pump2Warnings4 Bits See section 11.13 Alarms and warnings
00493 Pump2AntiBlockingCounter Bits Number of anti blockings in the pump
00494 Pump2AISetpointSelect enum
Analog input used as setpoint for pump 2:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00495 Pump2SetpointType enum
Setpoint type for pump 2:
0 = Fixed value
1 = Analog input
00496 Pump2FeedbackSensorType enum
Feedback sensor type for pump 2:
4 = Flow rate
5 = Level, pressure
6 = Level, ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00497 Pump2ControlMode enum
Control mode for pump 2:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00498 Pump2ActualSetpoint 1 % Actual setpoint for pump 2
00499 Pump2FixedFrequency 0.01 Hz Fixed frequency for pump 2
Address Register name Scale Description