9.10 Pump 3 register block
All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name Scale Description
00501
Pump3Status
Bit 0: Presence
Bool
Presence of pump.
0 = Not present
1 = Present.
Pump3Status
Bit 1: Running
Bool
Running state of pump.
0 = Not running
1 = Running.
Pump3Status
Bit 2: MonitoringFault
Bool
Fault state of pump monitoring devices.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
Pump3Status
Bit 3: Warning
Bool
Warning state of pump.
0 = No warning
1 = Warning.
Pump3Status
Bit 4: Alarm
Bool
Alarm state of pump.
0 = No alarm
1 = Alarm.
Pump3Status
Bit 5: IO111Present
Bool
Presence of auxiliary equipment IO 111.
0 = Not present
1 = Present.
Pump3Status
Bit 6: IO111Fault
Bool
Fault state of auxiliary equipment IO 111.
0 = No fault
1 = Fault.
Pump3Status
Bit 7: MP204Present
Bool
Presence of auxiliary equipment MP 204.
0 = Not present
1 = Present.
Pump3Status
Bit 8: MP204Fault
Bool
Fault state of auxiliary equipment MP 204.
0 = No fault
1 = Fault.
Pump3Status
Bit 9: CUEPresent
Bool
Presence of auxiliary equipment CUE.
0 = Not present
1 = Present.
Pump3Status
Bit 10: CUEFault
Bool
Fault state of auxiliary equipment CUE.
0 = No fault
1 = Fault.
Pump3Status
Bit 11: PumpDisabled
Bool
Enabled/disabled state of pump.
0 = Enabled
1 = Disabled (e.g. for temporary maintenance).
00502 Pump3ControlSource enum
Control source of pump.
0 = Auto
1 = Switch
2 = Display
3 = Remote-controlled by bus.
00503 Pump3ConnectionType enum
Pump connection type.
0 = The pump is controlled from the CU 36X output relay.
1 = The pump is controlled from the IO 351B output relay.
2 = The pump is controlled from the CU 36X and VFD.
3 = The pump is controlled from the IO 351B and VFD.
00504 Pump3OperatingTimeHI
1 minute Total operating time.
00505 Pump3OperatingTimeLO
00506 Pump3TimeToServiceHI
1 minute Time to next service.
00507 Pump3TimeToServiceLO
00508 Pump3OperatingTimeYesterday 1 minute Operating time yesterday.
00509 Pump3OperatingTimeToday 1 minute Operating time today.
00510 Pump3LatestOperatingTime 1 second Operating time last time it was operated.
00511 Pump3StartCounterHI
Unscaled Total number of pump starts.
00512 Pump3StartCounterLO
00513 Pump3StartCounterYesterday Unscaled Total number of pump starts yesterday.
00514 Pump3StartCounterToday Unscaled Total number of pump starts today.
00515 Pump3StartsPerHour Unscaled Number of pump starts within the last hour.
00516 Pump3Flow 0.1 litre/s Calculated average or measured pump flow.
00517 Pump3LatestFlow 0.1 litre/s Latest calculated/measured flow (capacity).