00518 Pump3Current 0.1 A Motor current.
00519 Pump3LatestCurrent 0.1 A Latest motor current.
00520 Pump3Voltage 0.1 V Voltage.
00521 Pump3Insulation 10 kΩ Motor insulation resistance.
00522 Pump3WaterInOil 0.1 % Motor water-in-oil measurement.
00523 Pump3Alarms1 Bits See section 11.13 Alarms and warnings
00524 Pump3Alarms2 Bits See section 11.13 Alarms and warnings
00525 Pump3Alarms3 Bits See section 11.13 Alarms and warnings
00526 Pump3Warnings1 Bits See section 11.13 Alarms and warnings
00527 Pump3Warnings2 Bits See section 11.13 Alarms and warnings
00528 Pump3Warnings3 Bits See section 11.13 Alarms and warnings
00529 Pump3MotorTemperature1 1 °C Motor temperature 1.
00530 Pump3MotorTemperature2 1 °C Motor temperature 2.
00531 Pump3PowerHI
1 W Power consumption.
00532 Pump3PowerLO
00533 Pump3EnergyHI
0.1 kWh Energy consumption.
00534 Pump3EnergyLO
00535 Pump3CosPhi 0.01 Motor cos φ.
00536 Pump3Frequency 0.1 Hz Motor-applied frequency.
00537 Pump3VFDmode enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00538 Pump3Torque 0.1 Nm Motor torque.
00539 Pump3Asym 0.1 % Line current asymmetry.
00540
Pump3Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump3Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00541 Pump3Alarms4 Bits See section 11.13 Alarms and warnings
00542 Pump3Warnings4 Bits See section 11.13 Alarms and warnings
00543 Pump3AntiBlockingCounter Bits Number of anti blockings in the pump
00544 Pump3AISetpointSelect enum
Analog input used as setpoint for pump 3:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00545 Pump3SetpointType enum
Setpoint type for pump 3:
0 = Fixed value
1 = Analog input
00546 Pump3FeedbackSensorType enum
Feedback sensor type for pump 3:
4 = Flow rate
5 = Level, pressure
6 = Level, ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00547 Pump3ControlMode enum
Control mode for pump 3:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00548 Pump3ActualSetpoint 1 % Actual setpoint for pump 3
00549 Pump3FixedFrequency 0.01 Hz Fixed frequency for pump 3
Address Register name Scale Description