9.11 Pump 4 register block
All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name Scale Description
00551
Pump4Status
Bit 0: Presence
Bool
Presence of pump.
0 = Not present
1 = Present.
Pump4Status
Bit 1: Running
Bool
Running state of pump.
0 = Not running
1 = Running.
Pump4Status
Bit 2: MonitoringFault
Bool
Fault state of pump monitoring devices.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
Pump4Status
Bit 3: Warning
Bool
Warning state of pump.
0 = No warning
1 = Warning.
Pump4Status
Bit 4: Alarm
Bool
Alarm state of pump.
0 = No alarm
1 = Alarm.
Pump4Status
Bit 5: IO111Present
Bool
Presence of auxiliary equipment IO 111.
0 = Not present
1 = Present.
Pump4Status
Bit 6: IO111Fault
Bool
Fault state of auxiliary equipment IO 111.
0 = No fault
1 = Fault.
Pump4Status
Bit 7: MP204Present
Bool
Presence of auxiliary equipment MP 204.
0 = Not present
1 = Present.
Pump4Status
Bit 8: MP204Fault
Bool
Fault state of auxiliary equipment MP 204.
0 = No fault
1 = Fault.
Pump4Status
Bit 9: CUEPresent
Bool
Presence of auxiliary equipment CUE.
0 = Not present
1 = Present.
Pump4Status
Bit 10: CUEFault
Bool
Fault state of auxiliary equipment CUE.
0 = No fault
1 = Fault.
Pump4Status
Bit 11: PumpDisabled
Bool
Enabled/disabled state of pump.
0 = Enabled
1 = Disabled (e.g. for temporary maintenance).
00552 Pump4ControlSource enum
Control source of pump.
0 = Auto
1 = Switch
2 = Display
3 = Remote-controlled by bus.
00553 Pump4ConnectionType enum
Pump connection type.
0 = The pump is controlled from the CU 36X output relay.
1 = The pump is controlled from the IO 351B output relay.
2 = The pump is controlled from the CU 36X and VFD.
3 = The pump is controlled from the IO 351B and VFD.
00554 Pump4OperatingTimeHI
1 minute Total operating time.
00555 Pump4OperatingTimeLO
00556 Pump4TimeToServiceHI
1 minute Time to next service.
00557 Pump4TimeToServiceLO
00558 Pump4OperatingTimeYesterday 1 minute Operating time yesterday.
00559 Pump4OperatingTimeToday 1 minute Operating time today.
00560 Pump4LatestOperatingTime 1 second Operating time last time it was operated.
00561 Pump4StartCounterHI
Unscaled Total number of pump starts.
00562 Pump4StartCounterLO
00563 Pump4StartCounterYesterday Unscaled Total number of pump starts yesterday.
00564 Pump4StartCounterToday Unscaled Total number of pump starts today.
00565 Pump4StartsPerHour Unscaled Number of pump starts within the last hour.
00566 Pump4Flow 0.1 litre/s Calculated average or measured pump flow.
00567 Pump4LatestFlow 0.1 litre/s Latest calculated/measured flow (capacity).