00668 Pump6Current 0.1 A Motor current.
00669 Pump6LatestCurrent 0.1 A Latest motor current.
00670 Pump6Voltage 0.1 V Voltage.
00671 Pump6Insulation 10 kΩ Motor insulation resistance.
00672 Pump6WaterInOil 0.1 % Motor water-in-oil measurement.
00673 Pump6Alarms1 Bits See section 11.13 Alarms and warnings
00674 Pump6Alarms2 Bits See section 11.13 Alarms and warnings
00675 Pump6Alarms3 Bits See section 11.13 Alarms and warnings
00676 Pump6Warnings1 Bits See section 11.13 Alarms and warnings
00677 Pump6Warnings2 Bits See section 11.13 Alarms and warnings
00678 Pump6Warnings3 Bits See section 11.13 Alarms and warnings
00679 Pump6MotorTemperature1 1 °C Motor temperature 1.
00680 Pump6MotorTemperature2 1 °C Motor temperature 2.
00681 Pump6PowerHI
1 W Power consumption.
00682 Pump6PowerLO
00683 Pump6EnergyHI
0.1 kWh Energy consumption.
00684 Pump6EnergyLO
00685 Pump6CosPhi 0.01 Motor cos φ.
00686 Pump6Frequency 0.1 Hz Motor-applied frequency.
00687 Pump6VFDmode enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00688 Pump6Torque 0.1 Nm Motor torque.
00689 Pump6Asym 0.1 % Line current asymmetry.
00690
Pump6Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump6Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00691 Pump6Alarms4 Bits See section 11.13 Alarms and warnings
00692 Pump6Warnings4 Bits See section 11.13 Alarms and warnings
00693 Pump6AntiBlockingCounter Bits Number of anti blockings in the pump
00694 Pump6AISetpointSelect enum
Analog input used as setpoint for pump 6:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00695 Pump6SetpointType enum
Setpoint type for pump 6:
0 = Fixed value
1 = Analog input
00696 Pump6FeedbackSensorType enum
Feedback sensor type for pump 6:
4 = Flow rate
5 = Level, pressure
6 = Level, ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00697 Pump6ControlMode enum
Control mode for pump 6:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00698 Pump6ActualSetpoint 1 % Actual setpoint for pump 6
00699 Pump6FixedFrequency 0.01 Hz Fixed frequency for pump 6