9.14 Alarm simulation register block
9.15 User register block
9.16 Name string register block
Address Register name Scale Description
00701 SimulationEventCode enum Event code to simulate.
00702 SimulationEventSource enum Event source to simulate.
00703 SimulationEventDeviceNo enum Event device number to simulate.
00704 SimulationEventActionType enum
0 = Warning
1 = Alarm
2 = Disabled.
00705 SimulationActivate Bool
Activation of simulation features.
0 = Deactivate simulation
1 = Activate simulation.
00706
SimulationStatus
Bit 0: SimulationActive
Bool
State of simulation.
0 = Not active
1 = Active.
Address Register name Scale Description
00751-00800 UserRegisters Unscaled
This area is for device labelling by the user. Neither the
CU 36X nor the CIM will modify this area.
The user area values are stored in the device and will
remain after a power-off.
Address Register name Scale Description
00801-00920 NameRegisterArea UTF-8 chars.
Name string read from the Dedicated Controls CU 36X.
UTF-8 is a variable-length character encoding for
Unicode. It can represent any character in the Unicode
standard.
It may take up to 60 seconds for a change to be visible.