9.20 Data log series register block
Data area for the configurable data log series (max. 64 series).
The log data are read-only and have a fixed starting address, so
log series 1 always starts at register 07301.
See section 11.3 Reading the configurable data log series for
detailed information on how to read the configurable log series.
… indicates variable register address.
Address Register name Scale Description
07301 LogSeries1ItemNo Unscaled
Log series 1 item number.
See section 11.3 Reading the configurable data log series.
07302 LogSeries1SamplingTime 1 second
Time period between samples in log series 1, configurable
on the CU 36X control panel.
07303 LogSeries1NoOfSamples Unscaled
Number of samples in log series 1, N
1
, configurable on the
CU 36X control panel.
07304 LogSeries1TimeStampHI
1 second
Log series 1 Unix time stamp. Subtracting "Sampling time"
gives the time stamp of sample No 2 in this series, etc.
07305 LogSeries1TimeStampLO
07306 LogSeries1Sample1 - Value of log series 1 sample No 1.
LogSeries1SampleN1 - Value of log series 1 sample No N
1
(last sample in series).
LogSeries2ItemNo -
Log series 2 item number.
See section 11.3 Reading the configurable data log series.
LogSeries2SamplingTime -
Time period between samples in log series 2, configurable
on the CU 36X control panel.
LogSeries2TimeStampHI
-
Log series 2 Unix time stamp. Subtracting "Sampling time"
gives the time stamp of sample No 2 in this series, etc.
LogSeries2TimeStampLO
LogSeries2Sample1 - Value of log series 2 sample No 1.
…… - -
LogSeries2SampleN2 - Value of log series 2 sample No N
2
(last sample in series).
LogSeries#ItemNo -
Log series # item number.
See section 11.3 Reading the configurable data log series.
LogSeries#SamplingTime - Time period between samples in log series #.
LogSeries#NoOfSamples - Number of samples in log series #, N
#
.
LogSeries#TimeStampHI
-
Log series # Unix time stamp. Subtracting "Sampling time"
gives the time stamp of sample No 2 in this series, etc.
LogSeries#TimeStampLO
LogSeries#Sample1 - Value of log series # sample No 1.
…… - -
LogSeries#SampleN# - Value of log series # sample No N
#
(last sample in series).
LogSeriesLItemNo -
Log series "L" item number.
See section 11.3 Reading the configurable data log series.
LogSeriesLSamplingTime - Time period between samples in log series "L".
LogSeriesLNoOfSamples - Number of samples in log series "L", N
L
.
LogSeriesLTimeStampHI
-
Log series "L" Unix time stamp. Subtracting "Sampling
time" gives the time stamp of sample No 2 in this series,
etc.
LogSeriesLTimeStampLO
LogSeriesLSample1 - Value of log series "L" sample No 1.
…… - -
LogSeriesLSampleN1 -
Value of log series "L" sample No N
L
(last sample in
series).