English (GB)
65
Pump alarms 1 (registers 00423 (pump 1), 00473 (pump 2), 00523 (pump 3), 00573 (pump 4), 00623 (pump 5), 00673 (pump 6))
Pump warnings 1 (registers 00426 (pump 1), 00476 (pump 2), 00526 (pump 3), 00576 (pump 4), 00626 (pump 5), 00676 (pump 6))
Motor temperature alarm, PTC1 PumpAlarms/warnings1.0 69 IO 111, pump No [1; 6]
Motor temperature alarm, PTC2 PumpAlarms/warnings1.1 70 IO 351B/MP 204/CUE, pump No [1; 6]
Motor stator temperature high (T1, Pt1000/Pt100) PumpAlarms/warnings1.2 64 IO 111/CUE, pump No [1; 6]
Motor stator temperature high (T2, Pt1000/Pt100) PumpAlarms/warnings1.3 71 MP 204, pump No [1; 6]
Motor support bearing temperature high (Pt100) PumpAlarms/warnings1.4 145 IO 111, pump No [1; 6]
Motor main bearing temperature high (Pt100) PumpAlarms/Warnings1.5 146 IO 111, pump No [1; 6]
Motor insulation resistance low PumpAlarms/Warnings1.6 20 IO 111/MP 204, pump No [1; 6]
Motor low voltage (no voltage) PumpAlarms/Warnings1.7 40 MP 204/CUE, pump No [1; 6]
Motor high voltage PumpAlarms/Warnings1.8 32 MP 204/CUE, pump No [1; 6]
Motor phase sequence reversal PumpAlarms/Warnings1.9 9 MP 204, pump No [1; 6]
Motor overload (maximum current) PumpAlarms/Warnings1.10 48 AI/MP 204/CUE, pump No [1; 6]
Motor underload (minimum current) PumpAlarms/Warnings1.11 56 AI/MP 204, pump No [1; 6]
Motor protector test trip PumpAlarms/Warnings1.12 27 DI/MP 204, pump No [1; 6]
Motor missing phase PumpAlarms/Warnings1.13 2 MP 204/CUE, pump No [1; 6]
Motor current asymmetry PumpAlarms/Warnings1.14 111 MP 204, pump No [1; 6]
Load continues even if the motor relay is off PumpAlarms/Warnings1.15 26 MP 204, pump No [1; 6]
Pump alarms 2 (registers 00424 (pump 1), 00474 (pump 2), 00524 (pump 3), 00574 (pump 4), 00624 (pump 5), 00674 (pump 6))
Pump warnings 2 (registers 00427 (pump 1), 00477 (pump 2), 00527 (pump 3), 00577 (pump 4), 00627 (pump 5), 00677 (pump 6))
Motor protector commanded (test) trip PumpAlarms/Warnings2.0 18 MP 204, pump No [1; 6]
Common phase error PumpAlarms/Warnings2.1 241 DI/CUE, pump No [1; 6]
Motor moisture switch PumpAlarms/Warnings2.2 22 IO 111, pump No [1; 6]
Motor/pump vibration high PumpAlarms/Warnings2.3 24 IO 111, pump No [1; 6]
Motor water-in-oil content too high (water in oil) PumpAlarms/Warnings2.4 11 AI/IO 111, pump No [1; 6]
Motor fault in mains supply PumpAlarms/Warnings2.5 6 DI, pump No [1; 6]
Motor contactor feedback fault PumpAlarms/Warnings2.6 220 DI, pump No [1; 6]
Motor max. starts per hour limit exceeded PumpAlarms/Warnings2.7 21 System, pump No [1; 6]
Motor operating time service limit exceeded PumpAlarms/Warnings2.8 12 Pump No [1; 6]
Too many pump auto-restarts (per 24 h) PumpAlarms/Warnings2.9 4 MP 204, pump No [1; 6]
Pump low flow PumpAlarms/Warnings2.10 58 Pump No [1; 6]
Pump max. continuous runtime limit exceeded PumpAlarms/Warnings2.11 245 System, pump No [1; 6]
Motor cos φ too high PumpAlarms/Warnings2.12 112 MP 204, pump No [1; 6]
Motor cos φ too low PumpAlarms/Warnings2.13 113 MP 204, pump No [1; 6]
Pump alarms 3 (registers 00425 (pump 1), 00475 (pump 2), 00525 (pump 3), 00575 (pump 4), 00625 (pump 5), 00675 (pump 6))
Pump warnings 3 (registers 00428 (pump 1), 00478 (pump 2), 00528 (pump 3), 00578 (pump 4), 00628 (pump 5), 00678 (pump 6))
Pump malfunction due to auxiliary component fault PumpAlarms/Warnings3.0 224 Pump No [1; 6]
Communication fault, pump module PumpAlarms/Warnings3.1 225 IO 111, pump No [1; 6]
On/Off/Auto switch fault PumpAlarms/Warnings3.2 244 DI, pump No [1; 6]
Signal fault, Pt100 sensor PumpAlarms/Warnings3.3 175 IO 111/MP 204/CUE, pump No [1; 6]
Signal fault, PTC sensor PumpAlarms/Warnings3.4 181 IO 111, pump No [1; 6]
Signal fault, water-in-oil (WIO) PumpAlarms/Warnings3.5 170 AI, pump No [1; 6]
Signal fault, bearing temperature sensor (Pt100),
general or top bearing
PumpAlarms/Warnings3.6 179 IO 111, pump No [1; 6]
Signal fault, bearing temperature sensor (Pt100),
middle bearing
PumpAlarms/Warnings3.7 180 IO 111, pump No [1; 6]
Communication fault, pump PumpAlarms/Warnings3.8 10 IO 111, pump No [1; 6]
Setup conflict PumpAlarms/Warnings3.9 25 IO 111, pump No [1; 6]
General hardware fault PumpAlarms/Warnings3.10 72 IO 111/MP 204, pump No [1; 6]
Signal fault, motor current sensor PumpAlarms/Warnings3.11 88 AI, pump No [1; 6]
Inrush fault PumpAlarms/Warnings3.12 155 CUE, pump No [1; 6]
Signal fault, sensor 2 PumpAlarms/Warnings3.13 93 CUE, pump No [1; 6]
Motor bearing temperature high (Pt100) in drive end
(DE)
PumpAlarms/Warnings3.14 148 CUE, pump No [1; 6]
Motor bearing temperature high (Pt100) in non-drive
end (NDE)
PumpAlarms/Warnings3.15 149 CUE, pump No [1; 6]
Description Data item Code Event source