00342 Pit4PumpsOprTimeToday 1 minute Operating time today (four pumps operating simultaneously).
00343 Pit5PumpsOprTimeHI
1 minute Total operating time (five pumps operating simultaneously).
00344 Pit5PumpsOprTimeLO
00345 Pit5PumpsOprTimeYesterday 1 minute Operating time yesterday (five pumps operating simultaneously).
00346 Pit5PumpsOprTimeToday 1 minute Operating time today (five pumps operating simultaneously).
00347 Pit6PumpsOprTimeHI
1 minute Total operating time (six pumps operating simultaneously).
00348 Pit6PumpsOprTimeLO
00349 Pit6PumpsOprTimeYesterday 1 minute Operating time yesterday (six pumps operating simultaneously).
00350 Pit6PumpsOprTimeToday 1 minute Operating time today (six pumps operating simultaneously).
00351 UserAnalogInput 1 0.1 % User-defined measurement, analog input 1.
00352 UserAnalogInput 2 0.1 % User-defined measurement, analog input 2.
00353 UserAnalogInput 3 0.1 % User-defined measurement, analog input 3.
00354 Pit0PumpsOprTimeHI
1 minute Total operating time (no pumps operating).
00355 Pit0PumpsOprTimeLO
00356 Pit0PumpsOprTimeYesterday 1 minute Operating time yesterday (no pumps operating).
00357 Pit0PumpsOprTimeToday 1 minute Operating time today (no pumps operating).
00358 Pit1PumpsOprTimeHI
1 minute Total operating time (one pump operating).
00359 Pit1PumpsOprTimeLO
00360 Pit1PumpsOprTimeYesterday 1 minute Operating time yesterday (one pump operating).
00361 Pit1PumpsOprTimeToday 1 minute Operating time today (one pump operating).
00362 MixerRuntime 1 minute Runtime for mixer.
00363 MixerStartCounter Unscaled Start counter for mixer.
00364 UserDefCounter1 Unscaled User-defined counter 1
00365 UserDefCounter2 Unscaled User-defined counter 2
00366 UserDefCounter3 Unscaled User-defined counter 3
00367 PitOutletPressure 0.001 bar Outlet pressure of the pit
00368 PitOverflowVolume32bitHI 0.1 m
3
Pit Overflow Volume, 32 bit value
00369 PitOverflowVolume32bitLO 0.1 m
3
Pit Overflow Volume, 32 bit value
00370 PitOverflowTime32bitHI 1 min Overflow time, 32 bit value
00371 PitOverflowTime32bitLO 1 min Overflow time, 32 bit value
00372 UserDefCounter1Today Unscaled User defined counter 1 today
00373 UserDefCounter2Today Unscaled User defined counter 2 today
00374 UserDefCounter3Today Unscaled User defined counter 3 today
00375 UserDefCounter1Yesterday Unscaled User defined counter 1 Yesterday
00376 UserDefCounter2Yesterday Unscaled User defined counter 2 Yesterday
00377 UserDefCounter3Yesterday Unscaled User defined counter 3 Yesterday
00378 H2SLevelActual 1 ppm Actual Hydrogen Sulfide (H2S) level
00379 H2SLevelToday 1 ppm Average Hydrogen Sulfide (H2S) level today
00380 H2SLevelYesterday 1 ppm Average Hydrogen Sulfide (H2S) level yesterday
00381 DosingFeedTankLevel 0.01 m Level in dosing feed tank
00382 DosingVolumeTotalHI
0.001 m
3
Dosed precipitation chemical volume in total
00383 DosingVolumeTotalLO
00384 DosingVolumeToday 0.001 m
3
Dosed precipitation chemical volume today
00385 DosingVolumeYesterday 0.001 m
3
Dosed precipitation chemical volume yesterday
00386 DosingRefActual 0.1 litre/h The actual chemical dosing reference (setpoint)
Address Register name Scale Description