00618 Pump5Current 0.1 A Motor current.
00619 Pump5LatestCurrent 0.1 A Latest motor current.
00620 Pump5Voltage 0.1 V Voltage.
00621 Pump5Insulation 10 kΩ Motor insulation resistance.
00622 Pump5WaterInOil 0.1 % Motor water-in-oil measurement.
00623 Pump5Alarms1 Bits See section 11.13 Alarms and warnings
00624 Pump5Alarms2 Bits See section 11.13 Alarms and warnings
00625 Pump5Alarms3 Bits See section 11.13 Alarms and warnings
00626 Pump5Warnings1 Bits See section 11.13 Alarms and warnings
00627 Pump5Warnings2 Bits See section 11.13 Alarms and warnings
00628 Pump5Warnings3 Bits See section 11.13 Alarms and warnings
00629 Pump5MotorTemperature1 1 °C Motor temperature 1.
00630 Pump5MotorTemperature2 1 °C Motor temperature 2.
00631 Pump5PowerHI
1 W Power consumption.
00632 Pump5PowerLO
00633 Pump5EnergyHI
0.1 kWh Energy consumption.
00634 Pump5EnergyLO
00635 Pump5CosPhi 0.01 Motor cos φ.
00636 Pump5Frequency 0.1 Hz Motor-applied frequency.
00637 Pump5VFDmode enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00638 Pump5Torque 0.1 Nm Motor torque.
00639 Pump5Asym 0.1 % Line current asymmetry.
00640
Pump5Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump5Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00641 Pump5Alarms4 Bits See section 11.13 Alarms and warnings
00642 Pump5Warnings4 Bits See section 11.13 Alarms and warnings
00643 Pump5AntiBlockingCounter Bits Number of anti blockings in the pump
00644 Pump5AISetpointSelect enum
Analog input used as setpoint for pump 5:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00645 Pump5SetpointType enum
Setpoint type for pump 5:
0 = Fixed value
1 = Analog input
00646 Pump5FeedbackSensorType enum
Feedback sensor type for pump 5:
4 = Flow rate
5 = Level, pressure
6 = Level, ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00647 Pump5ControlMode enum
Control mode for pump 5:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00648 Pump5ActualSetpoint 1 % Actual setpoint for pump 5
00649 Pump5FixedFrequency 0.01 Hz Fixed frequency for pump 5