13.2.2 Pit status display
Water level: PitWaterLevel (register 00301 [0.01 m]).
Pit depth: PitDepth (register 00303 [0.01 m]).
Actual flow: PitFlowOut (register 00306 [0.1 l/s]).
Average flow: PitAverageFlowOut (register 00307).
Total power consumption: PitPowerHI/LO (register 00308/
00309 [1 W]).
Total energy consumption: PitEnergyHI/LO (register 00310/
00311 [0.1 kWh]).
Energy consumption yesterday: PitEnergyYesterday (register
00312 [0.1 kWh]).
Energy consumption today: PitEnergyToday (register 00313
[0.1 kWh]).
Total pumping efficiency: PitSpecificEnergy (register 00314 [1
Wh/m
3
]).
Total operating time: PitOperatingTimeHI/LO (register 00329/
00330 [1 min.]).
Total pumped volume: PitPumpedVolumeHI/LO (register
00315/00316 [0.1 m
3
]).
Pumped volume yesterday: PitPumpedVolumeYesterday
(register 00317 [0.1 m
3
]).
Pumped volume today: PitPumpedVolumeToday (register
00318 [0.1 m
3
]).
Number of mixer starts per hour: PitMixerStartsPerHour
(register 00319).
Total overflow volume: PitOverflowVolume (register 00320 [0.1
m
3
]).
Overflow volume yesterday (24 h):
PitOverflowVolumeYesterday (register 00321 [0.1 m
3
]).
Overflow volume today: PitOverflowVolumeToday (register
00322 [0.1 m
3
]).
Total overflow time: PitOverflowTime (register 00323 [1 min.]).
Overflow time yesterday (24 h): PitOverflowTimeYesterday
(register 00324 [1 min.]).
Overflow time today (24 h): PitOverflowTimeToday (register
00325 [1 min.]).
Total number of overflows: PitOverflowCounter (register
00326).
Number of overflows yesterday (24 h):
PitOverflowCounterYesterday (register 00327).
Number of overflows today (24 h): PitOverflowCounterToday
(register 00328).
One-pump operating time: (Pump1OprTimeHI/LO +
Pump2OprTimeHI/LO - Pit2PumpsOprTimeHI/LO).
Two-pump operating time (two pumps operating
simultaneously): Pit2PumpsOprTimeHI/LO (register 00331/
00332 [1 min.]).
One-pump operating time yesterday (24 h):
(Pump1OprTimeYesterday + Pump2OprTimeYesterday -
Pit2PumpsOprTimeYesterday).
Two-pump operating time yesterday (two pumps operating
simultaneously): Pit2PumpsOprTimeYesterday (register 00333
[1 min.]).
Calculation of relative operating times:
– 1 pump = (Pump1OprTimeHI/LO + Pump2OprTimeHI/LO -
Pit2PumpsOprTimeHI/LO) / PitOperatingTimeHI/LO
(register 00329/00330)
– 2 pumps = Pit2PumpsOprTimeHI/LO / PitOperatingTimeHI/
LO.
Active alarms and warnings:
– PitAlarms1 (register 00210 [bits])
– PitAlarms2 (register 00211 [bits])
– PitAlarms3 (register 00212 [bits])
– PitWarnings1 (register 00213 [bits])
– PitWarnings2 (register 00214 [bits])
– PitWarnings3 (register 00215 [bits]).
13.2.3 Pump status display
The data item registers mentioned below are for pump 1. Adding
50 to the register addresses will give you the equivalent register
addresses for pump 2.
Operating mode (Started, Stopped): Pump1Status.Running
(register 00401, bit 1).
Control source (Auto, Switch, Display, Remote):
Pump1ControlSource (register 00402 [enum]).
Average flow: Pump1Flow (register 00416 [0.1 l/s]).
Latest measured flow: Pump1LatestFlow (register 00417 [0.1
l/s]).
Total number of pump starts: Pump1StartCounterHI/LO
(register 00411/00412).
Number of pump starts yesterday (24 h):
Pump1StartCounterYesterday (register 00413).
Number of pump starts today: Pump1StartCounterToday
(register 00414).
Number of pump starts per hour: Pump1StartsPerHour
(register 00415).
Total operating time: Pump1OprTimeHI/LO (register 00404/
00405 [1 min.]).
Operating time yesterday (24 h): Pump1OprTimeYesterday
(register 00408 [1 min.]).
Operating time today: Pump1OprTimeToday (register 00409 [1
min.]).
Latest operating time: Pump1LatestOprTime (register 00410
[1 s]).
Time to service: Pump1TimeToServiceHI/LO (register 00406/
00407 [1 min.]).
Motor temperature: Pump1MotorTemperature1 (register 00429
[1 °C]).
Motor current:
– Pump1Current (register 00418 [0.1 A])
– Pump1LatestCurrent (register 00419 [0.1 A]).
Motor, water in oil: Pump1WaterInOil (register 00422 [0.1 %]).
Commanding the pumps (Manual from Remote):
– Stop will issue the value PitPump1Control (register 00103
[enum]) = 2, which brings the pump into operating mode
Stop from Remote.
– Start will issue the value PitPump1Control (register 00103
[enum]) = 1, which brings the pump into operating mode
Start from Remote.
– Auto will issue the value PitPump1Control (register 00103
[enum]) = 0, which brings the pump back into its previous
state.
Note
The above information can be combined in a text like
"Operating mode" from "Control source".