An example is shown below
Event log
Hour log
The "Hour log" button opens the display for showing the hour
log. The table below illustrates the structure of the data in the
Modbus registers and a way of visualising them.
ID Code Description Source Type Time
341 192 Overflow System Alarm appearing 05-08-2008 09:25
342 192 Overflow System Alarm disappearing 05-08-2008 11:09
343 222 Time for service, mixer Mixer Warning appearing 07-08-2008 02:38
344 6 Motor insulation resistance low Pump 2 Warning appearing 11-08-2008 08:24
Note
The time stamp is in Unix time format. In the display
example, it has been converted to a human-readable
format.
Data
Hour
Registers
1 2 3 71 72
Pit overflow time [min.] 0 4 6 0 0 02001-02072
Number of pit overflows 0 1 3 0 0 02073-02144
Overflow volume [0.1 m
3
] 0 12 34 0 0 02145-02216
Specific energy [Wh/m
3
] 240 262 198 308 287 02217-02288
Pumped volume [m
3
] 67 69 72 45 23 02289-02360
Energy consumption [0.1 kWh] 342 456 514 178 123 02361-02432
Operating time (two pumps
operating simultaneously) [min.]
8 20 48 0 4 02433-02504
Pump 1, operating time [min.] 23 56 60 14 12 02793-02864
Pump 1, number of starts 4 1 1 4 3 02865-02936
Pump 1, average flow [0.1 l/s] 452 468 458 433 446 02937-03008
Pump 1, average current [0.1 A] 252 248 241 240 242 03009-03080
Pump 2, operating time [min.] 21 52 63 15 11 03081-03152
Pump 2, number of starts 7 2 1 2 3 03153-03224
Pump 2, average flow [0.1 l/s] 458 451 471 438 444 03225-03296
Pump 2, average current [0.1 A] 250 239 240 229 240 03297-03368