ID Object name R/W Description Unit LC 2X1 LC 2X2
AI, 40 Sensor present status R
Values are transmitted in the following order:
• bit 0: Flow sensor present
• bit 1: Power/energy sensor present
• bit 2: AI sensor 1 present
• bit 3: AI sensor 2 present
• bit 4: AI sensor 3 present
• bit 5: AI sensor 4 present
• bit 6: AI sensor 5 present
• bit 7: Turbidity sensor present
• bit 8: pH sensor present
• bit 9: Conductivity sensor present
• bit 10: Pulse flow meter present
• bit 11: Pressure sensor present
• bit 12: Level sensor present
Bit values indicate the following:
• bit value 0: Sensor not present
• bit value 1: Sensor present
- ● ●
AI, 41 Pump1 Alarms 1-4 and warnings 1-4 R
• bit 0 - Status pump 1 warning 1
• bit 1 - Status pump 1 warning 2
• bit 2 - Status pump 1 warning 3
• bit 3 - Status pump 1 warning 4
• bit 8 - Status pump 1 alarm 1
• bit 9 - Status pump1 alarm 2
• bit 10 - Status pump 1 alarm 3
• bit 11 - Status pump 1 alarm 4 (hex)
- ● ●
AI, 42 Pump2 Alarms 1-4 and warnings 1-4 R
• bit 0 - Status pump 2 warning 1
• bit 1 - Status pump 2 warning 2
• bit 2 - Status pump 2 warning 3
• bit 3 - Status pump 2 warning 4
• bit 8 - Status pump 2 alarm 1
• bit 9 - Status pump 2 alarm 2
• bit 10 - Status pump 2 alarm 3
• bit 11 - Status pump 2 alarm 4 (hex)
- ● ●
AI, 43 Pump1MotorVoltage R Pump1 MotorVoltage V ● ●
AI, 44 Pump2MotorVoltage R Pump2 MotorVoltage V ● ●
AI, 45 Pump1CosPhi R Pump1 CosPhi CosPhi ● ●
AI, 46 Pump2CosPhi R Pump2 CosPhi CosPhi ● ●
5.7 Analog outputs
Object for setting a new setpoint in the pump.
ID Object name R/W Notes Unit LC 2X1 LC 2X2
AO, 0 SetHighLevel W Set high level in centimetres. cm ● ●
AO, 1 SetDryRunningLevel W Set dry running level in centimetres. cm ● ●
AO, 2 SetStartLevelPump1 W Set start level for pump 1 in centimetres. cm ● ●
AO, 3 SetStopLevelPump1 W Set stop level for pump 1 in centimetres. cm ● ●
AO, 4 SetStartLevelPump2 W Set start level for pump 2 in centimetres. cm ● ●
5.8 Analog values
Objects for configuration of the module, the unit and the pump.
ID Object name R/W Notes Unit LC 2X1 LC 2X2
AV, 0
Custom device object instance
number
R/W
Present_Value range: 0-0x3FFFFE.
Default Present_Value: 0xE7. [RD = 0]
- ● ●
AV, 1 Product time and date R/W Set clock in UNIX format. s ● ●
AV, 2 CIMSoftwareVersionNumber R Decimal value - - ●
19
English (GB)