English (GB)
24
15. Technical data
15.1 Pump set
15.2 Sound pressure level
For more information on sound pressure level, see page 28.
The sound pressure is measured without a silencer and 1 m away
from the pump set.
15.3 Pump
For further performance data see nameplate of the pump.
15.3.1 Permissible flange forces and flange torques
Fig. 30 Flange forces and torques
* ΣF and ΣM are the vector sums of the forces and torques.
If not all loads reach the maximum permissible value, one of the
values may exceed the normal limit. Contact Grundfos for further
information.
15.4 Battery
Dimensions: See page 27.
Weight: See page 27.
The silencer supplied is designed for the
requirements of the industrial market. If you have
higher noise level requirements, you can order and
install another silencer.
Technical data: See page 27.
Rated flow: See nameplate of the pump.
Rated head: See nameplate of the pump.
Max. operating pressure: See nameplate of the pump.
Approval: See nameplate of the pump.
TM06 2665 4514
Grey cast iron
Flange
size
[inch]
Forces
[N]
Fx Fy Fz ΣF*
Horizontal pump
x-axis parallel to
pump shaft
2 890 2224 890 2555
2.5 1112 2780 1112 3194
3 1334 3336 1334 3832
4 1779 4448 1779 5110
5 2224 5560 2224 6388
6 2669 6672 2669 7666
8 3559 8896 3559 10221
10 4137 10364 4137 11901
12 4430 11103 4430 12749
14 4724 11841 4724 13596
16 5018 12580 5018 14444
18 5311 13318 5311 15290
20 5605 14056 5605 16137
24 6192 15533 6192 17831
30 7073 17748 7073 20373
Grey cast iron
Flange
size
[inch]
Torques
[Nm]
Mx My Mz ΣM*
Horizontal pump
x-axis parallel to
pump shaft
2 678 1356 678 1661
2.5 847 1695 847 2076
3 1017 2034 1017 2491
4 1356 2712 1356 3322
5 1695 3390 1695 4152
6 2034 4067 2034 4981
8 2712 5423 2712 6642
10 3390 6779 3390 8303
12 4067 8135 4067 9963
14 4745 9491 4745 11624
16 5423 10847 5423 13284
18 6101 12202 6101 14944
20 6779 13558 6779 16605
24 8135 16270 8135 19927
30 10169 20337 10169 24908
Pieces: 12 V - 1 per starter set
24 V - 2 per starter set
Battery voltage: 12 V
Starter set voltage: 12 or 24 V
Technical data: See page 28.
Do not charge the batteries by an external charger
when they are connected to the controller.