Grouting
Grouting compensates for uneven foundation,
distributes the weight of the unit, dampens vibrations
and prevents shifting. Use an approved, non-
shrinking grout. If you have questions or doubts about
the grouting, consult an expert on grouting.
Proceed as follows:
1. Build a strong formwork around the foundation to
contain the grout.
2. Soak the top of the concrete foundation
thoroughly, then remove surface water.
3. Fill the formwork with grout up to the bottom edge
of the base frame. See figure below. Allow the
grout to dry thoroughly before attaching the pipe
to the pump. 24 hours is sufficient time with
approved grouting procedure.
4. When the grout has thoroughly hardened, check
the anchor bolt nuts and tighten them if
necessary.
5. Approximately two weeks after the grout has been
poured, or when the grout has thoroughly dried,
apply an oil-based paint to the exposed edges of
the grout to prevent air and moisture from getting
in contact with the grout.
2
3
4
5
7
6
1
TM082324
Sectional view of foundation with anchor bolt,
grouting and base frame
Pos. Description
1 Base frame
2 Grout
3 Levelling wedges or shims left in place
4 Top of foundation left rough
5 19 to 32 mm grout
6 Formwork
7 5-10 mm
3.3 Electrical connection
The electrical connections must be carried out by an
authorised electrician in accordance with local
regulations.
DANGER
Electric shock
Death or serious personal injury
Before you remove the terminal box
cover and before you remove or dis-
mantle the pump, make sure that the
power supply has been switched off
and that it cannot be accidentally
switched on.
The operating voltage and frequency are marked on
the motor nameplate.
Make sure that the motor is suitable for the power
supply of the installation site.
Carry out the electrical connections as shown on the
motor nameplate or in the wiring diagram on the back
of the terminal box cover.
For further information, contact the motor supplier.
DANGER
Electric shock
Death or serious personal injury
Whenever you use powered equipment
in explosive surroundings, observe the
rules and regulations generally or spe-
cifically imposed by the relevant re-
sponsible authorities or trade organisa-
tions.
10
English (GB)

Other manuals for Grundfos LSV Series