6.3.2 Frequency of inspections
Carry out inspections in accordance with the
maintenance table below.
Depending on operating and environmental
conditions together with a comparison of previous
inspections, the frequency of inspections may be
altered to maintain satisfactory operation of the pump.
Every
week
Visually check for leaks.
Check for vibrations.
Hand test the bearing housing for
any sign of temperature rise.
Check correct leaking from the stuff-
ing boxes (approximately 40-60
drops per minute).
Every
month
Check the pump bearing tempera-
ture.
Every 6
months
Check the shaft for scores.
Check the alignment of the pump
and motor.
Check the fixing bolts and tighten, if
necessary.
Check the coupling for wear.
Every
year
Check whether the grease in the
pump bearings has hardened.
Check the rotating assembly for
wear.
Check the wear ring clearances.
CAUTION
Sharp element
Minor or moderate personal injury
Wear protective gloves to protect your-
self against sharp edges on the impel-
ler and wear rings.
Between the regular maintenance inspections, be
aware of signs of motor or pump trouble.
Common symptoms are listed in section Fault finding
the product.
Remedy any fault immediately and avoid costly
repairs and shutdowns.
6.3.3
Lubrication
Pump bearings
Pump bearings are lubricated before delivery.
We recommend relubricating at intervals of 2000
operating hours. However, depending on duty
conditions, this may vary.
To refill the bearings with fresh grease, follow this
procedure:
Recommend to use the same type of
grease. If need to replace the grease with
a new type, please clean up the old grease
and then add the new grease.
1. Remove the bearing cap.
2. Add enough grease to fill up 1/3 of the ball
bearing.
3. Note the quantity required.
4. Refit the bearing cap.
Grease quantity
Inlet size Grease quantity [g]
DN 65 to DN 100 11
DN 125 to DN 150 17
DN 200 to DN 300 25
DN 350 to DN 450 50
DN 500 60
DN 600 to DN 800 70
DN 1000 100
DN 1200 130
Repeat this procedure the first three times. Based on
the first three relubrications, determine the correct
quantity of grease required.
For future relubrications, apply the established
quantity of grease through the lubricating nipples. You
do not have to remove the bearing caps.
For every 10,000 operating hours or every two years:
1. Remove the bearing caps from the pump.
2. Remove old grease.
3. Thoroughly clean the bearing caps.
4. Refill the bearings with fresh grease.
5. Refill the bearing caps completely with fresh
grease.
6. Refit the bearing caps in accordance with the
assembly instructions.
7. Start the pump briefly several times to distribute
the grease in the bearings and to prevent
overheating of the grease.
Grease specifications: See section Ball-bearing
grease below.