APPENDIX
255
Current Accuracy
±0.4% F.S.
MEASUREMENT
VOLTAGE READBACK
Range 0~16V 0~80V
Resolution 0.5mV 2.5mV
Accuracy ±(0.05%set + 0.05% F.S.)
CURRENT READBACK
Range 0~2A 0~20A
Resolution 0.0625mA 0.625mA
Accuracy ±(0.1%set + 0.1% F.S.)
PROTECTIVE
Over Power Protection
Range 1~102W
Resolution 0.5W
Accuracy ±(2%set + 0.25% F.S.)
Over Current Protection
Range 0.25~20.4A
Resolution 0.05A
Accuracy ±(2%set + 0.25% F.S.)
Over Voltage Protection
Range 1~81.6V
Resolution 0.2V
Accuracy ±(2%set + 0.25% F.S.)
Over
Temperature
Protection
ؒ85Ԩ
Rated Power Protection
Value 110W
Accuracy ±2%set
GENERAL
SHORT CIRCUIT
Current(CC)
ؒ2.2/2A ؒ22/20A
Voltage(CV) 0V 0V
Resistance(CR)
ؒ3.75 ؒ0.075
INPUT
RESISTANCE
(LOAD OFF)
800K(Typical)