3
www.hager.com
6E 6380C
6E 6380C
X40 %
EG203E
§
2
channels electronic
time switch weekly cycle
User instructions
¢
Ech. 1
Keys:
menu : selection of operating mode
auto : mode of running according to the pro-
gram selected.
prog new for programming mode.
prog modif to modify an existing program.
: checking of the program.
: modification of time, date and
selection of the winter / summer time
change mode
.
: holidays.
+and- : navigation or setting of values.
A -: in auto, mode, selection of overrides,
B waivers or random operation
ok : to validate flashing information
on display.
: to return to the previous step.
You may return into auto mode at any moment
using menu.
If no action is taken for 1 minute, the switch
returns into auto mode.
à 40 %
à 40 %
auto
prog
modif
new
On
Off
24
1812
60
T
echnical specifications
Electrical characteristics
• Supply voltage 230 V AC ± 15%
• Frequency 50/60 Hz
• Power consumption max. 6 VA at 50 Hz
• Output 2 changeover volt free contacts
• Maximum load
AC1 µ16A 250 V~
Cos φ = 0,6 µ10A 250 V~
Incandescent lighting 2300 W
Halogen lighting 230 V 2300 W
Compensated fluorescent tubes //
(max. 45 µF) 400 W
Non compensated fluorescent tubes,
compensated in series 1000 W
Compact fluorescent lamps 500 W
• Minimum current.
AC1 100 mA 250 V~
• Galvanic insulation between power supply
and output < 4 kV
• Rated impulse voltage 4 kV
Functional characteristics
• Programming capacity 56 steps
• Minimum time between 2 steps 1 minute
• Running accuracy ± 1,5 sec / 24h
• Operating reserve lithium battery provides
5 years of backup.
• The product is set into standby state
(display switched-off) after 1 minute with
power off.
It switches back into auto mode as soon as
power is back or when pressing any key.
• Protection degree IP 20
• Action type 1B
• Degree of pollution 2
• Software class A
Environment
• Operating temperature -5 °C to +45 °C
• Storage temperature -20 °C to +70 °C
• Temperature for the ball pressure Test
75° to 125°C
Connection
• Flexible capacity 1 to 6 mm
2
• Rigid capacity 1,5 to 10 mm
2
Standards
60730-1
60730-2-7
Connection diagram
Resetting the program
The program can be totally deleted by pressing the following three keys simultaneously:
menu, ok, , the time and date are retained.
Reboot
Pressing the -, +, ok, menu keys simultaneously reboots the product.
auto
prog
modif
new
On
Off
24
1812
60
AI1_EG203_T1_02
ok
menu
+
produit à l'éch. 1
écran à 18 %
A B
auto
prog
modif
new
On
Off
24
1812
60
On
Off
1
2
34
AI1_EG203_T2_01
L
N
1357
2468
EG005
Major characteristics
Product delivered with current time and date set.
Automatic change of winter / summer time .
Programming key .
- for permanent overrides,
- for program copy or save.
Programming for day or group of days.
56 program steps On, Off or impulses (1 second to 30 minutes).
Permanent overrides On or Off ( permanent light on).
Temporary overrides On or Off ( flashing).
Holiday mode : overrides On or Off between two dates.
Simulation of presence .
Display bar graph of daily profile for both channels.
Keyboard locking possible .
Programmable with power off.
Back lit screen.
à 40 %
à
40 %
à 40 %
à 40 %
à 40 %