8
1 Contents
4. Technical specifications
Electrical specifications
Power supply voltage: 230V~ +10 / -15%
and 240V~ ± 6%
Network frequency: 50/60Hz
Consumption: EGN200AU < 350 mW /
EGN400AU < 500 mW
Output: 2 or 4 non-insulated changeover
contacts (depending on the version)
Max. break capacity: AC1 μ 16A 230V~
Incandescent lamps:
- Relay power with contact:
> normally open / 2300 W
> normally closed / 1500 W
Halogen lamps: 230V~ 2300W
Compensated fluorescent tubes // (max.
45 μF):
- Relay power with contact:
> normally open / 400 W
> normally closed / 300 W
Uncompensated fluorescent tubes,
compensated in series: 1000W
Compact fluorescent lamps and LED
lamps:
- Relay power with contact:
> normally open / 400 W
> normally closed / 300 W
Min. break capacity: AC1 100mA 230V~
Rated impulse withstand voltage: 4kV
Maximum switching rate at full load: 6
switching cycles / minute