powerway enclosures and components
System overview
20 U-PW powerway System Manual
03.01 System overview
powerway enclosures
U-PWE
U-PWK
Incoming and outgoing enclosure
Coupling enclosure
System solutions
hw+ series air circuit breaker (HW1)
Enclosure rated voltage
≤ 690 V AC
Expansion technology
Plug-in technology/fixed installation (version -F)
FFF, FFD/HW1
Plug-in insertion technology (version -W)
WWD/HW1
Enclosure rated current
Enclosure depth 600 mm
1x H-SaS
2950 A
2x H-SaS
2x 2600 A
Enclosure depth 800 mm
1x H-SaS
4000 A
2x H-SaS
2x 3800 A
Device installation position
Vertical
Extension/device operation
Full extension
From the outside, front installation level 1 (FE1)
Partial extension
Behind the door, behind front (HF)
Form of internal separation
1-4b
IP protection type
With convection
Devices can be operated from the outside
IP3x
[1]
With additional roof
IPx1
Without convection
Devices can be operated from the outside
IP3x
[1]
With additional roof
IPx1
[1]
In the case of withdrawable ACB in disconnected position
IP2xC