powerway enclosures and components
U-PWE/U-PWK
38 U-PW powerway System Manual
03.09 U-PWE/U-PWK
ACB incoming/outgoing/coupling enclosure 630-1600 A
ā Incoming units, outgoing units up to 1600 A
ā Cable outlets up to 1600 A
ā Cross couplings up to 1600 A
ā Device installation:
ā Measurement:
ā Connection type:
hw+ air circuit breakers
Field measurement
Cable connection enclosure roof and base,
busbar connection up to 1600 A
ā Either with 1 or 2 control compartments, installation position above or under the device
General characteristic features
⤠1600 A: 600 mm, number of device terminals: 3-pole/3-pole+NT
[1]
/4-pole
Enclosure heights
(without base)
2000 mm = 36 MU
2200 mm = 36 MU
H-SaS ⤠2950A: 600 mm
H-SaS ⤠4000A: 800 mm
[1]
Limitation, only first H-SaS position possible
Front-front ventilation
Front-roof ventilation
Base-front ventilation
Base-roof ventilation
IP30
IP30 (module roof IP40)
IP30
IP40 (module roof IP40)
Devices can be operated from the
outside
Devices behind the door
With additional roof
Devices can be operated from the
outside
Devices behind the door
With additional roof
[1]
In the case of withdrawable ACB in disconnected position IP2xC