 ..3 Indoor DC fan motor fault
Indoor display E14
DC fan motor is detected by checking the fan running condition and so on
when the data of EEPROM is error or the EEPROM is damaged
Conditions
Ƶ DC fan motor protection dues to the DC fan motor faulty
Ƶ DC fan motor protection dues to faulty PCB
* Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage
may be occurred.
Check whether Terminal on the indoor
mainboard is well inserted.
Is it normal?
Yes
NO
Reinsert the terminals
Electrify the machine again and turn it
on in the Cool state with the remote
controller. check whether motor can
run˛
Yes
Measure the voltage between 3 and 6 of
the terminal about 0-5v.
Is it normal?
N0
the motor of the indoor unit is damaged and
needs replacing.
Measure the voltage between 1 and 4 of the terminal of
fan motor on the mainboard about DC310V, Measure
the voltage between 4 and 5of the terminal about
DC15V. Measure the voltage between 4 and 6 of the
terminal about 1-6v.
NO
Is it normal?
The mainboard of the indoor unit is
damaged and needs replacing
N0
Yes
Yes
Service diagnosis
Domestic air conditioner

Supposed
Causes
Troubleshooting
parts damage may
Method of
malfunction detection
Malfunction detection
conditions